en | Installing
4.9

Wiegand Interface for Card Readers

Notice!
If your reader requires a voltage other than 12V or is the power consumption more than 200
mA then it will require an external power supply.
The AMC2-4W provides four ports for connecting a maximum of 4 readers with Wiegand
interfaces. Each interface is connected using a 10-pin pluggable screw - refer to Connecting
Diagrams, page 33 .
Figure 4.11: Location of the Wiegand interfaces for external devices
These interfaces are point-to-point connections, and each can support only a single reader
with a maximum cable length of 90 m (300 ft) for 24 AWG or 150 m (500 ft) for 22 AWG.
Readers are addressed according to their respective interface numbers.
Refer to Connecting Diagrams, page 33 for a complete wiring diagram of the Wiegand reader
interface .
4.10

Connecting Relay Outputs

To operate locks or alarm systems, the AMC2-4W has eight relay outputs. The outputs will be
connected to the 3-pin pluggable screw connectors S5, S6, S10, S11, S17, S18, S22, and S23
- refer to chapter Connecting Diagrams, page 33.