4.18 The Smart Plug
It is a function that displays the power consumption on the wired remote control when the outdoor unit is
operating.
■ Setting the function
Function
The Smart Plug
■ Option Selection
Setting
SPL0
oFF
Pd10
SPL1
Pd11
• Pd10 - Monitor the value from the watt hour meter.
• Pd11 - Monitor the calculated value in the outdoor unit. (error ± 5%)
■ Detailed information
• This function is used with heat pump and heat recovery.
• All modes is a change in the setting impact.
• When the optional PDI is installed, the PDI monitors outdoor unit power consumption as well as
indoor unit power consumption. PDI allocates outdoor unit power consumed to indoor units based
on the volume of refrigerant flow through each indoor unit during the billing period. For VRF systems
without the PDI, outdoor unit power consumption is reported, however indoor unit power consump-
tion is ignored.
• If the Smart Plug function is turned on, the power consumption data may be viewed using one of
LG's central control/monitoring devices such as ACP, AC Smart, or the multi site communications
manager. For installations where a third party BMS system Is present, consumption data is also
made available for viewing at the BMS front end using LG's BACnet gateway.
· Ask an authorized technician to setting a function.
· When PDI is installed, be sure to set the outdoor unit option to PDI ('PDI1').
(If the setting is not set to PDI1, the value displayed on the remote control may differ from the
actual value.)
· It is possible to check the power consumption during operation while setting the function, but it can
differ value compared to actual power consumption.
234
_TROUBLE SHOOTING GUIDE BOOK
Option
Fn 21
SPL0, SPL1, Pd10, Pd11
Detail of function
Smart Plug Logic OFF (Default)
PDI non-installation
PDI installation

4.19 Overall Defrost Entrance for Low temperature

It is a function to operate overall defrost.
■ Setting the function
Function
Overall Defrost Entrance for
Low temperature
■ Option Selection
Setting
on
oFF
■ Detailed information
• This function is used with heat pump and heat recovery.
• Heating modes is a change in the setting impact.
• Overall defrost operates every 3 hours whenever the outdoor air temperature is below 10℃. (If
defrosting is not possible for 3 hours)
• This function may be used in any location. It is most likely used in climates where moisture levels
are high the outdoor unit's heating capacity is slightly undersized, the condenser coil is partially
restricted, or other local factors dictate that no frost must be allowed to build on the coil.
· Ask an authorized technician to setting a function.
· If do not use a function, set an off-mode.
Option
Fn 22
on, oFF
Detail of function
Overall defrost
Default
235