Download Print this page

Bosch D7030X-S8 Installation Manual page 2

Eight-zone led annunciator

Advertisement

D7030X-S8 | Installation Guide |
Notices
This guide coves the installation of the D7030X-S8 Eight-Zone LED Annunicator in a fire system supervised by a
D7024 Fire Alarm Control Panel (FACP).
Install, test, and maintain the D7030X-S8 according to these instructions, NFPA 72, local codes, and the Authority
Having Jurisdiction (AHJ).
Follow the procedures in this guide to avoid personal injury and damage to the equipment. Failure to
follow procedures can cause the D7030X-S8 to not operate properly. Bosch is not responsible for
improperly installed, tested, or maintained devices.
1.0
Description
All eight zones of the D7030X-S8 are reserved for supervisory functions. This annunciator has power, trouble, and
eight zone LEDs that can be individually labeled. It mounts in a standard three-gang box (Figure 1).
Figure 1: D7030X-S8 Features
POWER
ON
SYSTEM
TROUBLE
FIRE SYSTEM
ANNUNCIATOR
1 - Front outside view
2 - Yellow zone LEDs (8)
3 - Inside view
4 - Address jumpers
5 - To D7031 (optional)
For the D7030X-S8 to operate with the D7024, use control panel firmware version 2.0 or greater.
2
Notices
1
2
1
8
Y
G
B
R
16 LED 8 LED 16 LED ENABLE
10
9
8
7
6 - LED enable jumpers
7 - 8 and 16 zone selection
8 - To D7032 (optional)
9 - To FACP option bus
10 - Remote LED pins
3
8
1
To CTRL-X
6
6
Bosch | 11/04 | 48176D