g
GE
Lighting Solutions
READ THOROUGHLY BEFORE INSTALLING
WARNING
Risk of electric shock
• Turn power off before servicing
– see instructions
WARNING
Risk of fire
• Use supply wire specified on
nameplate
G E N E R A L
This luminaire is designed for outdoor lighting
applications, and should not be used in areas of limited
ventilation, or in high ambient temperature enclosures. Best
results will be obtained if installed and maintained
according to the following recommendations.
WARNING: PAINFUL BURNS OF THE SKIN CAN
RESULT FROM TOUCHING OR HANDLING THE
FLOODLIGHT WHILE OPERATING.
The floodlight should not be installed in reach of the
general public, unless it is protected from accidental
handling, as the outside temperature of the housing, and
particularly the glass, can be sufficiently high to cause burns
of the skin. Floodlight should also be ordered with a door
that is screwed shut if the latches are in reach of the general
public. Criterion floodlights have both a screw-closure option
and tamper-resistant-screw option.
U N P A C K I N G
This luminaire has been properly packed so that no parts
should have been damaged during transit. Inspect to
confirm.
M O U N T I N G
CAUTION
Unit will fall if not installed properly
• Follow installation instructions
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation or
maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred
to GE Lighting Solutions.
Criterion
Follow installation instructions
1. Pipe Mounted units: The slipfitter can be mounted on
1-7/8-inch O.D. though 2-3/8-inch O.D. or 2-7/8 O.D.
through 3-inch O.D. pipes. Set screws are used to clamp
the floodlight securely to the pipe. Tighten set screws to 15
foot-pounds (20.3 N•m). Slipfitter is designed to mount on
a vertical pipe pointed upward such that gravity acts to
hold floodlight in place while the set screws are tightened.
Do not mount unit up-side-down.
Figure 1
Set Screws
2. Wall Mounted units: The wall mounting plate is provided
with four .438-inch clearance holes spaced 4.375(H) x
2.875(V) inches for mounting. Do not mount the unit
such that the hinge side of door is higher than the latch
side of door.
2.875 in
(73mm)
4 holes,
Figure 2
.438 in.
GEH-5874
INSTRUCTIONS
Floodlight
™
100 - 175 Watt
4.375 in