Haier 1U25BEEFRA Service Manual page 18

Wall mounted type dc inverter
Hide thumbs Also See for 1U25BEEFRA:
Table of Contents

Advertisement

3
4
5
6
7
8
Remarks: The above are the maximum frequency limitations of the complete appliance which are
affected by the environment, and they have nothing to do with the ability of the indoor unit.
Refrigeration/dehumidification mode:
Serial No.
1
2
3
4
5
6
7
Remarks: the above are not only the maximum frequency limitations of the complete appliance
which are affected by the environment, but also the maximum ability limitation of the system. When the
starting ability is not the maximum, its maximum frequency limitation is calculated by the following
equations:
The frequency limitation which is affected by the temperature and under the condition of actual
ability the actual running system ability*the maximum frequency which is limited by the temperature
and under the condition of maximum ability/the maximum designing ability of the system
Refrigeration/dehumidification mode:
The indoor setting
airflow speed
The percentage of the
rated frequency K
(09K)
Heating mode:
The indoor setting
airflow speed
The percentage of the
rated frequency K
(09K)
The calculation of the actual output frequency:
F= F-ED-*(rated frequency) K
F-ED-*(rated frequency)= The frequency which is limited by the outdoor environment temperature
Notes:
When refrigerating, it is needed to satisfy
Wh_c<-2
Wh_c<5
Wh_c<10
Wh_c<17
Wh_c<20
Wh_c> 20
Temperature scope
Wh_c<16
Wh_c<22
Wh_c<29
Wh_c<32
Wh_c<40
Wh_c<48
Wh_c>=48
Low
70%
Low
80%
Max_hz3
99HZ
Max_hz4
94HZ
Max_hz5
83HZ
Max_hz6
80HZ
Max_hz7
70HZ
Max_hz8
52HZ
Frequency limitation 09K
Max_hz1
39HZ
Max_hz2
43HZ
Max_hz3
49HZ
Max_hz4
61HZ
Max_hz5
68HZ
Max_hz6
57HZ
Max_hz7
38HZ
Medium
Quiet
85%
Medium
Quiet
90%
Domestic air conditioner
16
Functions and control
42%
50%

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents