Variable Speed Compressor; Wiring Error Check - Haier AW07EH2VHA Service Manual

Ductless multi-split heat pump
Table of Contents

Advertisement

Variable Speed Compressor

1. Begin by turning off power at the equipment disconnect switch. Adequate time must be given for capacitors on the circuit
board to discharge. Wait a minimum of 12 minutes before handling the circuitry.
2. Locate the Inverter control module (IPM). The IPM is connected to the main circuit board by a wire harnesses, and has the
compressor connections mounted on it.
3. Set your test meter to AC volts and test for voltage at the three compressor connections. Voltage should be zero before
proceeding.
4. Remove the three compressor connections making note of the terminal letter and the wire colors.
5. Set your ohm meter to the lowest resistance setting that is available. Test all three connections terminals using the following
sequence:
• U terminal to V terminal
• U terminal to W terminal
• V terminal to W terminal
All three resistance values should match the specification table below. Compressor windings are deemed bad if they are
greater than 7% out of specification. Readings taken at the wire IPM module that are outside of factory tolerances require
steps 6 through 9.
6. Remove the compressor blanket and set it aside. Remove the terminal block cover to expose the connections at the
compressor terminals. Inspect for any visual damage. Remove all three wires from the terminals making note of the wire color
and the terminal identifier.
7. Repeat process outlined in step 5. Repair or replace the wires if the compressor windings check properly.
8. Check each terminal to ground (suction line connection at compressor) to check for grounded windings if the resistance
values are not correct.
9. Replace the compressor if the winding measurements are greater than 7% out of specification.

Wiring Error Check

1. Disconnect power to
the outdoor unit.
2. Set Dip Switches
SW1-1, SW1-2,
SW1-3 & SW1-4 to
the ON position.
These dip switches
are located on the
Service Monitor
Board.
3. Turn ON power to the outdoor unit.
4. All indoor fans will be set to HIGH fan speed.
5. EEV for Circuit A will open. All other EEV's will close.
6. After a 3 minute delay, the Compressor will start and ramp
up to 55HZ.
7. The digital display with alternately display "CH" and
"Compressor Frequency (HZ)" at 5 second intervals
Testing
8. The system will circulate refrigerant through Circuit A for
9. Afterwards, Circuit A's EEV will close and Circuit B's EVV
10. This process will be repeated for each indoor unit that is
11. Once all indoor units have
12. Once the wiring is corrected, re-run this test to confirm
13. "0" indicates that all wiring is
14. If all wiring is correct, the
15. Once the test is complete,
OUTDOOR TECHNICAL OVERVIEW
approximatley 10 minutes.
will open.
connected.
been checked, the digital
display will display either
"EC" or "0". "EC" indicates
a communication error
between the outdoor and
indoor unit. The LED(s) will
be flashing, indicating which
circuit has the fault
everything is functional.
correct.
LED's remain solid lit.
make sure to change the dip
switches back to the OFF
position, and set each indoor
unit to preferred set points.
B-17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents