Fig. 8-5: Female connector strip is plugged on

4. Secure the female connector strip in place with a screw-type locking
to prevent it from slipping out.
A separate conductor must always be provided for the protective groun-
ding at the threaded bolt. The conductor must have a minimum cross-
section of 1.5 mm² (16 AWG) and must be kept as short as possible.
Only use a damp cloth to remove any dirt from the front panel.
The semiconductor fuse cannot be replaced!
A semiconductor fuse is used to protect the device. Once the fuse has
been tripped, the device must be disconnected from the supply voltage
to allow the semiconductor fuse to regenerate. At an ambient tempera-
ture of 20 °C (68° F), the regeneration takes approximately 20
seconds. The higher the ambient temperature, the longer the regenera-
tion takes.