IndraControl XFE01.1-SY-01 Safety Ex-
tension Module
NOTICE
The operating height of the entire system is reduced from 4700 m to 2000 m
The ambient temperature of the entire system in operation reduces from the
range between -25°C and +60°C to the range between + 5°C and +55°C
NOTICE
Due to the risk of corrosion, avoid sulphurous gases (e.g. sulphur dioxide (SO
and hydrogen suphide (H
NOTICE
The ambient air must not contain acids, alkaline solutions, corrosive agents,
salts, metal vapors and other electrically conductive contaminants in high
concentrations
The devices to be installed into the housing and installation compartments
must at least comply with the degree of protection IP 54 according to DIN EN
60529.
The device shall be provided in a suitable fire enclosure in the end-use
application.
This is a product that corresponds to the limit values of the emitted
interference of class A (industrial environments), but not of class B
(residential area and small enterprises).
When using the product in residential areas or small enterprises, the
operator has to take actions to prevent radio interferences (also
refer to DIN EN 55022).

7 Technical data

7.1 Voltage supply

The Safety extension module IndraControl XFE01.1-SY-01 is supplied with 12 V
via a separate connection.
The input voltage of the Safety extension module is 24 V DC (as per the
requirements acc. to DIN EN 61131-2). The voltage is supplied from PELV power
supply units with safe separation acc. to EN 50178 and EN 60950-1.
Due to the ambient conditions required to
operate the Safety extension modules, the
following restrictions result for the entire
system
Defective product due to gases jeopardizing
functions
S)). The product is not resistant against these gases.
2
Failure of the product due to contaminated air
R911376654_Edition 03 Bosch Rexroth AG