Specifications; Troubleshooting - Panasonic KT2 Communication Instruction Manual

Hide thumbs Also See for KT2:
Table of Contents

Advertisement

03H
00A1H: Instrument information reading

8. Specifications

Communication method
Cable length
Communication line
Number of connectable units: Maximum 31 units
Communication speed
Synchronous system
Instrument number
Communication protocol
Code form
Error detection
Error correction
Data format

9. Troubleshooting

If any malfunction occurs, refer to the following items after checking the power supply to the master
and the slave.
• Problem: Communication failure
The connection or wiring of the communication cable is not secure.
Burnout or imperfect contact on the communication cable and the connector.
Communication speed of the slave does not coincide with that of the master.
The data bit, parity and stop bit of the master do not accord with those of the slave.
The instrument number of the slave does not coincide with that of the command.
The instrument numbers are duplicated in multiple slaves.
When communicating without using communication converter, make sure that the program is
appropriate for the transmission timing.
• Problem: Although communication is occurring, the response is 'exception code'.
Check whether a non-existent command code has been sent or not.
The setting command data exceeds the setting range of the slave.
The controller cannot be set when functions such as AT is performed.
While in setting mode and inputting settings via the front keypad.
For further inquiries, please consult our agency or the shop where you purchased the unit.
Panasonic Industrial Devices SUNX Co., Ltd.
http://panasonic.net/id/pidsx/global
Overseas Sales Division (Head Office)
2431-1 Ushiyama-cho, Kasugai-shi, Aichi, 486-0901, Japan
Phone: +81-568-33-7861 FAX: +81-568-33-8591
About our sale network, please visit our website.
PRINTED IN JAPAN
Pursuant to the directive 2004/108/EC, article 9(2)
Panasonic Electric Works Europe AG
Rudolf-Diesel-Ring 2 83607 Holzkirchen, Germany
This product has been developed / produced for industrial use only.
: Half-duplex
: Maximum communication distance 1,000m
Cable resistance: Within 50
: EIA RS-485
: 9600bps (2400, 4800, 9600, 19200bps) Selectable by keypad
: Start-stop synchronous
: 0 (0 to 95) Selectable by keypad
: Modbus ASCII (Modbus ASCII, Modbus RTU) Selectable by keypad
: ASCII (Modbus ASCII) , Binary (Modbus RTU) (*)
: Parity, LRC (Modbus ASCII), CRC (Modbus RTU) (*)
: Command request repeat system
Start bit : 1 bit
Data bit : 7 bits (Modbus ASCII), 8 bits (Modbus RTU) (*)
Parity
: Even (Modbus ASCII), No parity (Modbus RTU) (*)
Stop bit : 1 bit
(*): Automatically selected upon selecting the communication protocol.
Check the following
Check the following
© Panasonic Industrial Devices SUNX Co., Ltd. 2012
12
0000 0000 0000 0000
15
2
to
0
2
digit: OUT1 (Heating) output
0: OFF 1: ON (For current
output, Not decided)
1
2
digit: Heating/Cooling function option
0: Not applied 1: Applied
2
2
digit: A1 function
0: Not applied 1: Applied
3
2
digit: A2 function
0: Not applied 1: Applied
4
15
2
to 2
digit: Not used (Always 0)
(The terminator is not necessary or
120
or more on the PLC side.)
0
2