GFK-2749
Parameter
IBx Gain
VCxL Gain
VCxH Gain
ICx Gain
INx Gain
Chapter 3 Configuration and Data Transfer
Function
Calibration constant. Value provided on the ACC200
Terminal Assembly label.
Improves the accuracy of the current measurement of
channel 4 (IB). This value can be further adjusted to
compensate for inaccuracies of external Current
Transformers and wiring.
Range: 0h to FFFFh
Default: 4000h
Calibration constant. Value provided on the ACC200
Terminal Assembly label.
Improves the accuracy of the 120V range of channel 5 (VC).
This value can be further adjusted to compensate for
inaccuracies of external Potential Transformers and wiring.
Range: 0h to FFFFh
Default: 4000h
Calibration constant. Value provided on the ACC200
Terminal Assembly label.
Improves the accuracy of the 600V range of channel 5 (VC).
This value can be further adjusted to compensate for
inaccuracies of external Potential Transformers and wiring.
Range: 0h to FFFFh
Default: 4000h
Calibration constant. Value provided on the ACC200
Terminal Assembly label.
Improves the accuracy of the current measurement of
channel 6 (IC). This value can be further adjusted to
compensate for inaccuracies of external Current
Transformers and wiring.
Range: 0h to FFFFh
Default: 4000h
Calibration constant. Value provided on the ACC200
Terminal Assembly label.
Improves the accuracy of the current measurement of
channel 7 (IN). This value can be further adjusted to
compensate for inaccuracies of external Current
Transformers and wiring.
Range: 0h to FFFFh
Default: 4000h
3
3-5