Safety precaution WARNING ● Never use this product as a sensing device for personnel protection. ● In case of using devices for personnel protection, use products which meet laws and standards, such as OSHA, ANSI or IEC etc., for personnel protection applicable in each region or country.
Part Description Thru-beam front sensing type: EX-11□ , EX-13□ , EX-19□, EX-11S□ , EX-13S□ , EX-19S□ Stability indicator (Green) Operation indicator Mounting (Orange) hole Mounting hole Beam Beam receiving emitting part part <Emitter> <Receiver> Thru-beam side sensing type: EX-11E□ , EX-13E□ , EX-19E□ EX-11SE□...
Page 5
Thru-beam front sensing type with Thru-beam side sensing type with operation mode switch on bifurcation: operation mode switch on bifurcation: EX-15, EX-17 EX-15E, EX-17E <Emitter> <Receiver> <Emitter> <Receiver> Stability indicator (Green) Beam Mounting Mounting emitting Operation indicator(Orange) hole hole Mounting Mounting part hole...
Mounting 3-1 Mounting of the sensor ● The tightening torque should be 0.2 N·m or less. ● The narrow beam type EX-1□S□ emits a narrow light beam, so it is difficult to align the beam. Note that if screws or other parts become loose due to vibration, for example, the beam axis may drift.
3-2 Mounting interval ● This product does not incorporate auto interference function. In case mounting two sets or more of the this product close together, please mount them as drawing below indi- cates (typical example) ● Find out the operating point ℓ on the parallel deviation diagram for the setting distance L. Separate sensors by 2 ×...
Page 8
Thru-beam type: EX-13□, EX-17□ parallel deviation diagram (typical) <Installation interval for EX-13□,EX-17□> In case using at sensing distance (L3) 500mm, the operation point (ℓ3) is approx. 76.6mm according to diagram above. (L3) The installation interval is Approx. 76.6mm × 2 = approx. 153.2mm (ℓ3) Thus, install approx.
Page 9
Thru-beam type: EX-19□, parallel deviation diagram (typical) <Installation interval for EX-19□> In case using at sensing distance (L5) 1m, the operation point (ℓ5) is approx. 128.6mm (L5) according to diagram above. The installation interval is (ℓ5) Approx. 128.6mm × 2 = approx. 257.2mm Thus, install approx.
Page 10
Thru-beam type: EX-11S□, parallel deviation diagram (typical) <Installation interval for EX-11S□> In case using at sensing distance (L7) 150mm, the operation point (ℓ7) is approx. (L7) 10.8mm according to diagram above. The installation interval is (ℓ7) Approx. 10.8mm × 2 = approx. 21.6mm Thus, install approx.21.6 or more away.
Page 11
Thru-beam type: EX-13S□, parallel deviation diagram (typical) <Installation interval for EX-13S□> In case using at sensing distance (L9) 500mm, the operation point (ℓ9) is approx. 37.1mm according to diagram above. (L9) The installation interval is Approx. 37.1mm × 2 = approx. 74.2mm (ℓ9) Thus, install approx.74.2 or more away.
Page 12
Thru-beam type: EX-19S□, parallel deviation diagram (typical) <Installation interval for EX-19S□> In case using at sensing distance (L11) 1m, the operation point (ℓ11) is approx. (L11) 65.4mm according to diagram above. The installation interval is (ℓ11) Approx. 65.4mm × 2 = approx. 130.8mm Thus, install approx.130.8 or more away.
Stability Indicator ● The stability indicator (green) lights up when the incident light intensity has sufficient margin with respect to the operation level. Incident light intensity level is such that the stability indicator light up, stable sensing can be done without the light received operation and the light interrupted operation being af- fected by a change in ambient temperature or supply voltage.
Option 7-1 Slit Mask (optional) ● Apply the optional slit mask OS-EX10-□ when detecting small objects or for increasing the accuracy of sensing position. However, the sensing range is reduced when the slit mask is mounted. Model No. Sensing distance Minimal sensing object Type Slit size...
Specifications 8-1 Standard-beam type Convergent reflective Thru-beam type (Diffused Type beam type) Front sensing Side sensing Front sensing Side sensing Front sensing Side sensing Front sensing Light-ON EX-11A(-PN) EX-11EA(-PN) EX-13A(-PN) EX-13EA(-PN) EX-19A(-PN) EX-19EA(-PN) EX-14A(-PN) Model No (Note 2) Dark-ON EX-11B(-PN) EX-11EB(-PN) EX-13B(-PN) EX-13EB(-PN)
Page 17
Thru-beam · with operation mode switch on bifurcation Type Front sensing Side sensing Front sensing Side sensing EX-15 EX-15E EX-17 EX-17E Model No. (Note 2) (Note 5) Sensing range 150mm 500mm ø1 mm opaque object ø2 mm opaque object Minimum sensing (Completely beam interrupted object) (Completely beam interrupted object) object...
8-2 Narrow-beam type Thru-beam type Type Front sensing Side sensing Front sensing Side sensing Front sensing EX-11SA(-PN) EX-11SEA(-PN) EX-13SA(-PN) EX-13SEA(-PN) EX-19SA(-PN) Light-ON Model No (Note 2) EX-11SB(-PN) EX-11SEB(-PN) EX-13SB(-PN) EX-13SEB(-PN) EX-19SB(-PN) Dark-ON Sensing range 150mm 500mm ø0.5mm opaque ø1mm opaque ø1mm opaque object ø2mm opaque object ø2mm opaque object...