6.6.4 TRLYS1D Specifications

Item
Number of Relay Channels
Rated Voltage on Relays
Wetting Power, JF1/JF2
Relay Contact Rating for 24 V dc
Solenoids
Relay Contact Rating for 125 V dc
Solenoids
Maximum Response Time On
Maximum Response Time Off
Contact Life
FU1 – FU12 Fuse Rating
Board Size
Fault Detection
Size

6.6.5 TRLYS1D Diagnostics

Diagnostic tests to components on the terminal boards are as follows:
The solenoid excitation voltage is monitored downstream of the fuses and an alarm is latched if it falls below 12 V dc.
If any one of the outputs goes unhealthy a composite diagnostics alarm, L3DIAG_xxxx occurs.
Each terminal board connector has its own ID device that is interrogated by the I/O pack. The connector ID is coded into
a read-only chip containing the board serial number, board type, revision number, and the JA1/JR1/JS1/JT1 connector
location. When the chip is read by the I/O pack and mismatch is encountered, a hardware incompatibility fault is created.
Details of the individual diagnostics are available in the configuration application. The diagnostic signals can be
individually latched, and then reset with the RSTDIAG signal if they go healthy.
154
GEH-6855_Vol_II
TRLYS1D Specification
Six relays with special customer solenoid monitoring
Nominal 125 or 24 V dc
13.5 A max
Current rating 2.25 A, resistive
Current rating 2 A, L/R = 7 ms, without suppression
Current rating 0.5 A, resistive
Current rating 0.2 A, L/R = 7 ms, without suppression
Current rating 0.5 A, L/R = 150 ms, with suppression (MOV) across the load
25 ms typical
25 ms typical
Electrical operations: 100,000
3.15 A, 500 V ac / 400 V dc, 5 x 20 mm time-lag
17.8 x 33.0 cm (7 x 13 in)
Loss of solenoid voltage supply (fuse monitor)
Solenoid resistance measured to detect open and short circuits
Unplugged cable or loss of communication with I/O pack (relays de-energize if
communication with associated I/O pack is lost)
17.8 wide x 33.02 cm high (7.0 x 13.0 in)
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II