Unsuccessful Auto Tune; Set Speed Limit And Accel/Decel Times - GE AF-600 FP Operating Instructions Manual

Fan and pump drive (460v/575v 150hp and above)
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Unsuccessful auto tune

1.
The frequency converter enters into alarm mode. A description of the alarm can be found in the Warnings and Alarms chapter.
2.
"Report Value" in the [Alarm Log] shows the last measuring sequence carried out by the auto tune, before the frequency converter entered alarm mode.
This number along with the description of the alarm will assist you in troubleshooting. If you contact GE for service, make sure to mention number and
alarm description.
NB!
Unsuccessful auto tune is often caused by incorrectly entering motor name plate data or a too big difference between the motor power size and the frequency
converter power size.
Step 4. Set speed limit and accel/decel times.
par. F-52 Minimum Reference
par. F-53 Maximum Reference
Table 3.18: Set up the desired limits for speed and ramp time.
par. F-18 Motor Speed Low Limit [RPM] or par. F-16 Motor Speed
Low Limit [Hz]
par. F-17 Motor Speed High Limit [RPM] or par. F-15 Motor
Speed High Limit [Hz]
par. F-07 Accel Time 1
par. F-08 Decel Time 1
AF-600 FP High Power Operating Instructions