Set-Points Data Tables

The following tables are quick references for control variables, ranges, and defaults.
Not all variables are available on every unit.
Table 15: Temperature Control Set-Points Data Table.
Control Variable
Reset Control Mode - Temperature Control
Mode Selection
Temperature Set-point
Heat / Cool Deadband
Supply Set-points - Cooling Mode
Maximum
Minimum
Supply Set-points - Heating Mode
Maximum
Minimum
Outside Set-points - Outside Reset
Maximum
Minimum
Mode Switch Delay
Startup Delay
Cooling Ambient Lockout
Heating Ambient Lockout
Pre-heat
Ambient Lockout
OAD En. Pos.
Unoccupied Cooling
Set-point
Hysteresis
Unoccupied Heating
Set-point
Hysteresis
Winter Ramp
Enable
Mode
OAT Enable
Case Heat Set-point
Set-point availability varies based on unit configuration.
Default
Min.
Space Reset
72.0°F
50.0°F
4.0 Δ°F
0.0 Δ°F
100.0°F
70.0°F
50.0°F
50.0°F
100.0°F
70.0°F
55.0°F
50.0°F
80.0°F
-30.0°F
30.0°F
-30.0°F
120 sec.
30 sec.
30 sec.
0 sec.
55.0°F
30.0°F
80.0°F
30.0°F
10.0°F
-40.0°F
30%
80.0°F
65.0°F
5.0 Δ°F
0.0 Δ°F
60.0°F
50.0°F
5.0 Δ°F
0.0 Δ°F
Disabled (□) Disabled (□)
Supply Fan
Supply Fan
40.0°F
20.0°F
40.0°F
0.0°F
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Max.
Supply Temp. Control, Space Reset,
Return Reset, Outside Reset
100.0°F
20.0 Δ°F
100.0°F
70.0°F
100.0°F
70.0°F
130.0°F
130.0°F
600 sec.
600 sec.
100.0°F
100.0°F
65.0°F
0%
100%
85.0°F
10.0 Δ°F
70.0°F
10.0 Δ°F
Enabled (X)
Outside Damper
70.0°F
100.0°F
CONTROLLER
Set-Points Data Tables
Notes
129