ACS 753, ACS 763, ACS 863 Service Manual
PAG Load Cell Calibration
1. With the Calibrate Load Cell menu displayed,
use the up/down arrow keys to toggle to the
PAG Load Cell service menu. The following
displays:
2. Select OK icon to enter the PAG Load Cell
calibration menu. The following displays:
3. Select OK icon to begin the calibration.
Selecting ESC icon returns to the Calibrate
Load Cell service menu.
Follow all remaining calibration instructions
displayed.
• First point calibration without nothing.
• Second point calibration with 500 g (edit-
able).
• Check with 250 g (not editable) and con-
firm with OK icon.
NOTE: DO NOT DISTURB unit during weight
calibration.
Robert Bosch GmbH
Diagnostics and Testing
POE Load Cell Calibration
1. With the Calibrate Load Cell menu displayed,
use the up/down arrow keys to toggle to the
POE Load Cell service menu. The following
displays:
2. Select OK icon to enter the POE Load Cell
calibration menu. The following displays:
3. Select OK icon to begin the calibration.
Selecting ESC icon returns to the Calibrate
Load Cell service menu.
Follow all remaining calibration instructions
displayed.
• First point calibration without nothing.
• Second point calibration with 500 g (edit-
able).
• Check with 250 g (not editable) and con-
firm with OK icon.
NOTE: DO NOT DISTURB unit during weight
calibration.
31
SP00D00609
2018-03-26