Power Card Mounting Plate - GE AF-650 GP Operating Instructions Manual

High power unit sizes 6x
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

9.2.3 Power Card Mounting Plate

1.
Disconnect two fast-on connectors from fuse block attached to power card mounting plate flange.
2.
Disconnect from power card connectors MK100, MK103, MK104, MK105, MK106, and MK110.
3.
Disconnect three cable connectors (6-pin, 8-pin, and 12-pin) from power card mounting panel flange. Cable connectors disconnect from back side of
flange.
4.
Remove power card mounting plate by removing four retaining nuts (8mm) securing plate.
NOTE: At this point soft charge cards are accessible for changing fuses. Two soft charge cards are present for units with two inverter modules, three
soft charge cards for units with three inverter modules.
6
1
Power card mounting plate (step 4)
2
Power card (step 2)
3
Cable connectors (step 3)
1
4
5
6
High Power Service Manual for Unit Sizes 6x
2
3
Fuse block (step 1)
Power card mounting plate flange
Attaching screw (step 4)
4
5
9
123

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Af-600 fp

Table of Contents