Open Fuse Lock Out Device; Akd- 5 Interlock - GE AK-2A-15 User Maintenance Manual

Power circuit breaker
Table of Contents

Advertisement

OPEN FUSE LOCK OUT DEVI CE
(Figure 3 1 )
The Open Fuse Lockout Device consists of
two or three separately operated devices (one per
phase).
Each wired in parallel to corresponding
breaker fuses.
This device is furnished on
AKU breakers.
The purpose
to trip the breaker upon the blowing of any one of
the breaker fuses and render the breaker trip
free until the blown fuse is replaced and the
associated coil assembly reset.
OPERATION, Figure 3 1 .
When any one of the breaker fuses blow, the
coil (6) in that phase is energized and the armature
(5) closes.
With the armature closed, leaver (2)
slips under the armature and latches it in the
closed position.
The latched closed armature
holds the breaker in the trip free position until
it is released by pushing the associated reset
button (1).
The coil is deenergized as soon as
the breaker opens.
ADJUSTMENTS
1 .
Set top cylindrical collor (not shown) to engage
the trip shaft paddle in the tripped position.
)
:
Figure 3 1 . (804 1865) Open Fuse Lockout Device
1 .
Mounting Holes
2 .
Lever
3 .
Reset Button
4 .
Collor
5 .
Armature
6.
Coil
3 6
all
of
this device is
2 .
Check that each armature holds the breaker
trip free when the armature position is limited
in reset by the lower latch surface on the
indicator.
3.
With the breaker in the closed position, the
top collor must clear the trip shaft paddle
by more than 1/32 inch.
REPLACE MENT
1.
Remove three mounting screws at top
device .
2 .
Remove coil leads from fuses and work wire
harness back to the device.
from breaker .
3 .
Replace new unit in reverse order and check
procedure under ADJUSTMENTS.

AKD- 5 INTERLOCK

(Figure 32)
The rackout mechanism is interlocked so that
the circuit breaker must be open before the
operating handle can be inserted.
breaker is closed, the interlock link (1 ) operated
by the breaker cross bar blocks the interlock
linkage on the rackout mechanism
Figure 32. (803 9852 ) AKD-5 Interlock
1 .
Rackout Mechanism Interlock
2 .
Trip Interlock
.,
4
of
Remove device
When the

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents