Relion
670 series
Line differential protection RED670
Pre-configured
Product Guide

Advertisement

loading

Summary of Contents for ABB RED670

  • Page 1 ® Relion 670 series Line differential protection RED670 Pre-configured Product Guide...
  • Page 2: Table Of Contents

    5. Hardware description.........28 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumes no responsibility for any errors that may appear in this document.
  • Page 3: Application

    RED670 is used for the protection, control under- and overvoltage functions are and monitoring of overhead lines and cables examples of the available functions allowing in all types of networks.
  • Page 4 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 The packages are configured and ready for For details on included basic functions refer direct use. Optional functions are not to section "" configured but a maximum configuration...
  • Page 5 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 BUS A TRIP BUSBAR &CB2 CLOSE O->I SC/VC 94/86 TRIP I->O O->I SC/VC 50BF 50/51 3I> 3I> TRIP 50BF CB1/3 3I> 94/86 I->O 3Id/I> 3U>...
  • Page 6: Available Functions

    Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 2. Available functions ANSI Function description Single breaker, 3- Multi breaker, 3- Singel breaker, 1- Multi breaker, 1- phase tripping phase tripping phase tripping phase tripping...
  • Page 7 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 ANSI Function description Single breaker, 3- Multi breaker, 3- Singel breaker, 1- Multi breaker, 1- phase tripping phase tripping phase tripping phase tripping (A31) (B31)
  • Page 8 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 ANSI Function description Single breaker, 3- Multi breaker, 3- Singel breaker, 1- Multi breaker, 1- phase tripping phase tripping phase tripping phase tripping (A31) (B31)
  • Page 9: Functionality

    Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 ANSI Function description Single breaker, 3- Multi breaker, 3- Singel breaker, 1- Multi breaker, 1- phase tripping phase tripping phase tripping phase tripping (A31) (B31)
  • Page 10 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Protected zone Comm. Channel en05000039.vsd IEC05000039 V1 EN Figure 3. Example of application on a conventional two-terminal line The six terminal versions are used for...
  • Page 11 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 harmonic restraint and zero-sequence current elimination. Protected zone Comm. Channel Comm. Channel Comm. Channel en05000042.vsd IEC05000042 V1 EN Figure 5. Example of application on a three-terminal line with a power transformer in the...
  • Page 12 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Protected zone Comm. Channels en05000044.vsd IEC05000044 V1 EN Figure 7. Five terminal line with master-slave system Current samples from IEDs located where transmit and receive times can differ,...
  • Page 13 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 to detect high resistive faults on heavily measuring and settings, which gives high loaded lines. flexibility for all types of lines. The IED can be used up to the highest voltage levels.
  • Page 14 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 sensitivity of the mho element due to the Faulty phase identification with load shaping of the curve at remote end faults. encroachment FMPSPDIS The integrated control and monitoring...
  • Page 15 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 A 2nd harmonic blocking can be set Pole slip protection PSPPPAM individually for each step. Sudden events in an electrical power system Instantaneous residual overcurrent...
  • Page 16 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 inputs or the current from a separate current A contact check criteria can be used where input. the fault current through the breaker is small.
  • Page 17 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 auxiliary contacts of the circuit breaker for Two step overvoltage protection OV2PTOV the three phases with additional criteria from can be used as open line end detector, unsymmetrical phase current when required.
  • Page 18 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 used for generation shedding, load shedding, Loss of voltage check LOVPTUV remedial action schemes. SAPFRC can discriminate between positive or negative Loss of voltage check (LOVPTUV) is suitable change of frequency.
  • Page 19 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 A detection of a difference indicates a fault in SESRSYN function includes a built-in voltage the circuit and is used as alarm or to block selection scheme for double bus and 1½...
  • Page 20 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 the IEDs communicate via the system-wide have the capability to receive commands (for interbay bus (IEC 61850-8-1) or by using hard example, SCSWI). In this way, simple wired binary inputs/outputs.
  • Page 21 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 the part of the line not covered by its The weak-end infeed logic is used in cases underreaching zone. where the apparent power behind the •...
  • Page 22 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 residual overcurrent protection (ECRWPSCH) sufficient length, as well as all functionality function. necessary for correct co-operation with autoreclosing functions. Current reversal and weak-end infeed logic...
  • Page 23 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 outputs where one is inverted. The memory Supervision of mA input signals (MVGGIO) setting controls if the block after a power interruption should return to the state The main purpose of the function is to before the interruption, or be reset.
  • Page 24 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 time to the end of post-fault time will be The event recorder logs all selected binary included in the recording. input signals connected to the Disturbance report function.
  • Page 25 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 operation of protection functions. It can Measured value expander block RANGE_XP record disturbances not detected by protection functions. The current and voltage measurements functions (CVMMXU, CMMXU, VMMXU and...
  • Page 26 GOOSE is part of the standard. Disturbance files uploading is provided. Serial communication, LON Existing stations with ABB station bus LON can be extended with use of the optical LON interface. This allows full SA functionality including peer-to-peer messaging and cooperation between existing ABB IED's and the new IED 670.
  • Page 27 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 functionality is mainly used for the line IEC 60870-5-103 communication protocol differential protection. However it can be used in other products as well. An IED can A single glass or plastic port is provided for communicate with up to 4 remote IEDs.
  • Page 28: Hardware Description

    Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 5. Hardware description mA input module MIM The milli-ampere input module is used to Hardware modules interface transducer signals in the –20 to +20 mA range from for example OLTC position, Power supply module PSM temperature or pressure transducers.
  • Page 29 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 secondary currents and voltages generated by Galvanic RS485 serial communication the measuring transformers. The module has module twelve inputs in different combinations of The galvanic RS485 serial communication currents and voltage inputs.
  • Page 30 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 xx05000004.vsd IEC05000004 V1 EN Figure 12. Side-by-side mounting Case size 6U, 1/2 x 19” 265.9 223.7 201.1 242.1 252.9 205.7 6U, 3/4 x 19” 265.9 336.0...
  • Page 31: Connection Diagrams

    Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 6. Connection diagrams Table 1. Designations for 1/2 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM or IOM X31 and X32 etc. to X51...
  • Page 32 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 2. Designations for 3/4 x 19” casing with 2 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X71 and...
  • Page 33 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 3. Designations for 1/1 x 19” casing with 2 TRM slots Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X131 IOM or MIM...
  • Page 34 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 IEC08000479 BG V1 EN Figure 13. Transformer input module (TRM) ■ Indicates high polarity CT/VT-input designation according to figure AI01 AI02 AI03 AI04 AI05 AI06...
  • Page 35 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 IEC08000484 BG V1 EN Figure 15. mA input module (MIM) IEC08000480 BG V1 EN Figure 14. Binary input module (BIM). Input contacts named XA corresponds to...
  • Page 36 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 IEC08000477 BG V1 EN Figure 16. Communication interfaces (OEM, LDCM, SLM and HMI) Note to figure Rear communication port SPA/IEC 61850-5-103, ST-connector for glass alt. HFBR Snap-in connector for plastic as ordered Rear communication port LON, ST connector for glass alt.
  • Page 37 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 IEC08000478 BG V1 EN Figure 18. GPS time synchronization module (GSM) IEC08000481 BG V1 EN Figure 19. Binary output module (BOM). Output contacts named XA corresponds to rear position X31, X41, and so on, and output contacts named XB to rear position X32, X42, and so on.
  • Page 38 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 IEC08000482 BG V1 EN Figure 20. Static output module (SOM) IEC08000483 BG V1 EN Figure 21. Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41, and so on, and output contacts named XB to rear position X32, X42, and so on.
  • Page 39: Technical Data

    Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 7. Technical data General Definitions Reference The specified value of an influencing factor to which are referred the value characteristics of the equipment Nominal The range of values of an influencing quantity (factor) within which, under...
  • Page 40 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 5. MIM - mA input module Quantity: Rated value: Nominal range: Input resistance = 194 Ohm Input range ± 5, ± 10, ± 20mA...
  • Page 41 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Binary inputs and outputs Table 8. BIM - Binary input module Quantity Rated value Nominal range Binary inputs RL ± 20% DC voltage, RL 24/40 V 48/60 V RL ±...
  • Page 42 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 10. IOM - Binary input/output module Quantity Rated value Nominal range Binary inputs RL ± 20% DC voltage, RL 24/40 V 48/60 V RL ± 20% 110/125 V RL ±...
  • Page 43 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 12. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs Function of quantity Static binary output trip Rated voltage 48 - 60 VDC...
  • Page 44 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 13. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage...
  • Page 45 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Influencing factors Table 15. Temperature and humidity influence Parameter Reference value Nominal range Influence Ambient +20 °C -10 °C to +55 °C 0.02% /°C temperature, operate...
  • Page 46 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Type tests according to standards Table 18. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-22-1, Class III...
  • Page 47 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 19. Insulation Test Type test values Reference standard Dielectric test 2.0 kV AC, 1 min. IEC 60255-5 5 kV, 1.2/50 ms, 0.5 J Impulse voltage test Insulation resistance >100 MW at 500 VDC...
  • Page 48 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Differential protection Table 23. High impedance differential protection (PDIF, 87) Function Range or value Accuracy Operate voltage (20-400) V ± 1.0% of U for U < U ±...
  • Page 49 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Impedance protection Table 25. Distance measuring zone, Quad ZMQPDIS Function Range or value Accuracy Number of zones 3 with selectable direction Minimum operate (5-30)% of IBase...
  • Page 50 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 26. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS Function Range or value Accuracy Number of zones 3 with selectable direction -...
  • Page 51 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 27. Full-scheme distance protection, Mho characteristic ZMHPDIS Function Range or value Accuracy Number of zones with 3 with selectable selectable directions direction Minimum operate current (10–30)% of I...
  • Page 52 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 28. Phase selection with load encroachment, quadrilateral characteristic Function Range or value Accuracy Minimum operate current (5-30)% of IBase ± 1.0% of IBase Reactive reach, positive (0.50–3000.00) Ω/phase...
  • Page 53 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 30. Power swing detection ZMRPSB Function Range or value Accuracy (0.10-3000.00) W/phase Reactive reach ± 2.0% static accuracy Conditions: Voltage range: (0.1-1.1) x U Current range: (0.5-30) x I...
  • Page 54 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Current protection Table 33. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy ± 1.0% of I at I £ I Operate current (1-2500)% of lBase ±...
  • Page 55 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 34. Four step phase overcurrent protection OC4PTOC Function Setting range Accuracy ± 1.0% of I at I £ I Operate current (1-2500)% of lBase ±...
  • Page 56 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 35. Instantaneous residual overcurrent protection EFPIOC Function Range or value Accuracy ± 1.0% of I at I £ I Operate current (1-2500)% of lBase ±...
  • Page 57 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 36. Four step residual overcurrent protection EF4PTOC Function Range or value Accuracy ± 1.0% of I at I £ I Operate current (1-2500)% of lBase ±...
  • Page 58 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 37. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy ± 1.0% of I at I £ I (0.25-200.00)% of lBase Operate level for 3I ·cosj...
  • Page 59 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 37. Sensitive directional residual overcurrent and power protection SDEPSDE , continued Function Range or value Accuracy Operate time, non 60 ms typically at 0 to 2 x I...
  • Page 60 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 39. Breaker failure protection CCRBRF Function Range or value Accuracy ± 1.0% of I at I £ I Operate phase current (5-200)% of lBase ±...
  • Page 61 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 42. Directional underpower protection GUPPDUP Function Range or value Accuracy Power level (0.0–500.0)% of Sbase ± 1.0% of S at S < S ± 1.0% of S at S > S At low setting: (0.5-2.0)% of Sbase...
  • Page 62 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Voltage protection Table 45. Two step undervoltage protection UV2PTUV Function Range or value Accuracy Operate voltage, low and (1–100)% of UBase ± 1.0% of U...
  • Page 63 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 47. Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy Operate voltage, low and (1-200)% of Ubase ± 1.0% of U at U < U high step ±...
  • Page 64 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 49. Voltage differential protection (PTOV) Function Range or value Accuracy Voltage difference for (0.0–100.0) % of U ± 0.5 % of U base alarm and trip Under voltage level (0.0–100.0) % of U...
  • Page 65 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 52. Overfrequency protection SAPTOF Function Range or value Accuracy Operate value, start function (35.00-75.00) Hz ± 2.0 mHz at symmetrical three-phase voltage Operate time, start function...
  • Page 66 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Multipurpose protection Table 54. General current and voltage protection (GAPC) Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, NegSeq, 3*ZeroSeq, MaxPh, MinPh, UnbalancePh,...
  • Page 67 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 54. General current and voltage protection (GAPC), continued Function Range or value Accuracy Voltage level where voltage (0.0 - 5.0)% of U ± 1.0% of U...
  • Page 68 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 54. General current and voltage protection (GAPC), continued Function Range or value Accuracy Undervoltage: Critical impulse time 10 ms typically at 2 to 0 x U...
  • Page 69 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Control Table 57. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line (0.40-25.000) % of UBase...
  • Page 70 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 58. Autorecloser SMBRREC Function Range or value Accuracy Number of autoreclosing shots 1 - 5 Number of autoreclosing programs Autoreclosing open time: shot 1 - t1 1Ph (0.000-60.000) s...
  • Page 71 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Scheme communication Table 59. Scheme communication logic for distance or overcurrent protection ZCPSCH Function Range or value Accuracy Scheme type Intertrip Permissive Underreach Permissive Overreach...
  • Page 72 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 61. Current reversal and weak-end infeed logic for distance protection ZCRWPSCH Function Range or value Accuracy Detection level phase-to- (10-90)% of UBase ± 1.0% of U...
  • Page 73 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 64. Current reversal and weak-end infeed logic for phase segregated communication (PSCH, 85) Function Range or value Accuracy Detection level phase to (10-90)% of U ±...
  • Page 74 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 66. Configurable logic blocks Logic block Quantity with cycle time Range or value Accuracy fast medium normal LogicAND LogicOR LogicXOR LogicInverter LogicSRMemory LogicGate LogicTimer (0.000–90000.000) s...
  • Page 75 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 68. Supervision of mA input signals (MVGGIO) Function Range or value Accuracy mA measuring function ± 5, ± 10, ± 20 mA ± 0.1 % of set value ± 0.005 mA...
  • Page 76 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 70. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–1.00) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings...
  • Page 77 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 72. Event list Function Value Buffer capacity Maximum number of events in 1000 the list Resolution 1 ms Accuracy Depending on time synchronizing Table 73. Indications...
  • Page 78 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 76. Disturbance recorder Function Value Buffer capacity Maximum number of analog inputs Maximum number of binary inputs Maximum number of disturbance reports 100 Maximum total recording time (3.4 s recording time and...
  • Page 79 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 81. SPA communication protocol Function Value Protocol Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd Slave number 1 to 899 Table 82. IEC 60870-5-103 communication protocol...
  • Page 80 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 85. Galvanic X.21 line data communication module (X.21-LDCM) Quantity Range or value Connector, X.21 Micro D-sub, 15-pole male, 1.27 mm (0.050") pitch Connector, ground selection...
  • Page 81 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 87. Line data communication module Characteristic Range or value Type of LDCM Short range Medium range Long range (LR) (SR) (MR) Type of fibre...
  • Page 82 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 88. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) Table 89.
  • Page 83 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Basic IED functions Table 93. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 1000 events, first in-first out Table 94.
  • Page 84 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 97. IRIG-B Quantity Rated value Number of channels IRIG-B Number of channels PPS Electrical connector IRIG-B Optical connector PPS and IRIG-B Type ST Type of fibre 62.5/125 μm multimode fibre...
  • Page 85 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 99. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-999) in steps of 0.01 æ ö ç ÷ ×...
  • Page 86 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 100. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic k = (0.05-999) in steps of 0.01...
  • Page 87 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 101. Inverse time characteristics for Two step undervoltage protection (PUVM, 27) Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of Class 5 +40 ms 0.01...
  • Page 88 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 102. Inverse time characteristics for Two step overvoltage protection (POVM, 59) Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of Class 5 +40 ms 0.01...
  • Page 89 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Table 103. Inverse time characteristics for Two step residual overvoltage protection (POVM, 59N) Function Range or value Accuracy Type A curve: k = (0.05-1.10) in Class 5 +40 ms steps of 0.01...
  • Page 90: Ordering

    Exemple code: RED670*1.1-A31-A03B01C04F01-X0-A-A-B-A-A6X0-DAS-AA-XD. Using the code of each position #1-12 specified as RED670*1-2 2-3 3 3 3 3 3 3 3-4 4-5-6-7 7-8-9 9 9-10 10 10 10 10 10 10 10 10 10 10-11 11 11 11 11 11-12 12...
  • Page 91 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Software options Notes and Rules No option All fields in the ordering form do not need to be filled in High impedance differential protection Line differential protecion 6 CT sets,...
  • Page 92 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Casing Notes and Rules 1/2 x 19" case Note: Only 1/2 case for A31/A32 3/4 x 19" case 2 TRM slots 1/1 x 19" case 2 TRM slots Selection for position #5.
  • Page 93 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Binary input/output module, mA Notes and Rules and time synchronizating boards. Note: 1BIM and 1 BOM included In A31/A32/B31/B32, 1 IOM basic in A21. Slot position (rear view)
  • Page 94 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Remote end communication, DNP serial comm. Notes and Rules and time synchronization modules Slot position (rear view) Available slots in 1/2 case with 1TRM Note: Only for A31/A32. 1 LDCM in A31/A32.
  • Page 95 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 Basic IED functions Self-supervision with internal event list Time and synchronization error Time synchronization Parameter setting groups Test mode functionality Change lock function IED Identifiers...
  • Page 96 IED 670 products is described in Multi-breaker/Single or Three Phase trip with 1MRK 512 001-BEN and 1MRK 001024-CA. internal neutral on current circuits (ordering Please refer to the website: www.abb.com/ number RK926 315-BE). substationautomation and ABB Product Multi-breaker/Single or Three Phase trip with Guide >...
  • Page 97 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 External resistor unit for high impedance differential protection High impedance resistor unit 1-ph with resistor 1.8 kOhms and Quantity: RK795101-MA voltage dependent resistor for 20-100V operating voltage High impedance resistor unit 3-ph with resistor 1.8 kOhms and...
  • Page 98 Line differential protection RED670 1MRK 505 188-BEN C Pre-configured Product version: 1.1 Issued: June 2010 User documentation Rule: Specify the number of printed manuals requested Quantity: 1MRK 505 184-UEN Operator’s manual ANSI Quantity: 1MRK 505 184-UUS Technical reference manual Quantity:...
  • Page 99 IEC 61850 Data objects list for IED 670, ver. 1.1 1MRK 500 084-WEN Engineering guide IED 670 products 1MRK 511 179-UEN Communication set-up for RED 670 Differential protection and 670 series 1MRK 505 197-UEN More information can be found on www.abb.com/substationautomation.
  • Page 101 Contact us ABB AB Substation Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 +46 (0) 21 14 69 18 www.abb.com/substationautomation...