B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 32 of 60)
ADDR
REGISTER NAME
7233
Neutral Directional Overcurrent 1 Forward ECA
7234
Neutral Directional Overcurrent 1 Forward Limit Angle
7235
Neutral Directional Overcurrent 1 Forward Pickup
7236
Neutral Directional Overcurrent 1 Reverse Limit Angle
7237
Neutral Directional Overcurrent 1 Reverse Pickup
B
7238
Neutral Directional Overcurrent 1 Target
7239
Neutral Directional Overcurrent 1 Block
723B
Neutral Directional Overcurrent 1 Events
723C
Neutral Directional Overcurrent 1 Polarizing Voltage
723D
Neutral Directional Overcurrent 1 Op Current
723E
Neutral Directional Overcurrent 1 Offset
723F
Neutral Directional Overcurrent 1 Pos Seq Restraint
7240
Reserved
7241
...Repeated for Neutral Directional Overcurrent 2
Breaker Arcing Current Settings (Read/Write Setting) (2 modules)
7290
Breaker 1 Arcing Current Function
7291
Breaker 1 Arcing Current Source
7292
Breaker 1 Arcing Current Initiate A
7294
Breaker 1 Arcing Current Initiate B
7296
Breaker 1 Arcing Current Initiate C
7298
Breaker 1 Arcing Current Delay
7299
Breaker 1 Arcing Current Limit
729A
Breaker 1 Arcing Current Block
729C
Breaker 1 Arcing Current Target
729D
Breaker 1 Arcing Current Events
729E
...Repeated for Breaker 2 Arcing Current
Disconnect (Breaker) Switch (Read/Write Setting) (8 modules)
74A0
Disconnect Switch 1 Function
74A1
Disconnect Switch 1 Name
74A4
Disconnect Switch 1 Mode
74A5
Disconnect Switch 1 Open
74A7
Disconnect Switch 1 Block Open
74A9
Disconnect Switch 1 Close
74AB
Disconnect Switch 1 Block Close
74AD
Disconnect Switch 1 Phase A / Three-pole Closed
74AF
Disconnect Switch 1 Phase A / Three-pole Opened
74B1
Disconnect Switch 1 Phase B Closed
74B3
Disconnect Switch 1 Phase B Opened
74B5
Disconnect Switch 1 Phase C Closed
74B7
Disconnect Switch 1 Phase C Opened
74B9
Disconnect Switch 1 Operate Time
74BA
Disconnect Switch 1 Alarm Delay
74BC
Disconnect Switch 1 Events
74BD
Reserved (2 items)
74BF
...Repeated for Disconnect Switch 2
74DE
...Repeated for Disconnect Switch 3
74FD
...Repeated for Disconnect Switch 4
751C
...Repeated for Disconnect Switch 5
753B
...Repeated for Disconnect Switch 6
755A
...Repeated for Disconnect Switch 7
7579
...Repeated for Disconnect Switch 8
Thermal Overload Protection (Read/Write Settings) (2 modules)
7788
Thermal Protection 1 Function
7789
Thermal Protection 1 Source
B-40
RANGE
-90 to 90
40 to 90
0.006 to 30
40 to 90
0.006 to 30
0 to 2
0 to 4294967295
0 to 1
0 to 1
0 to 1
0 to 250
0 to 0.5
0 to 1
0 to 1
0 to 5
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 50000
0 to 4294967295
0 to 2
0 to 1
0 to 1
---
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 65.535
0 to 1
---
0 to 1
0 to 5
L30 Line Current Differential System
APPENDIX B
UNITS
STEP
FORMAT
° Lag
1
F002
degrees
1
F001
pu
0.001
F001
degrees
1
F001
pu
0.001
F001
---
1
F109
---
1
F300
---
1
F102
---
1
F231
0 (Calculated V0)
---
1
F196
0 (Calculated 3I0)
ohms
0.01
F001
---
0.001
F001
---
1
F001
---
1
F102
---
1
F167
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
2
kA
-cyc
1
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
s
0.001
F003
---
1
F102
---
---
F001
---
1
F102
---
1
F167
DEFAULT
75
90
50
90
50
0 (Self-reset)
0
0 (Disabled)
0
63
0
0 (Disabled)
0 (SRC 1)
0
0
0
0
1000
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
"SW 1"
0 (3-Pole)
0
0
0
0
0
0
0
0
0
0
70
0
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)