Chapter 4 Connection and Settings
4.1 Setting the ETERNUS DX/AF
■
ETERNUS DX8700 S3/DX8900 S3
This section explains the setting items on the power synchronization setting screen for the ETERNUS DX8700
S3/DX8900 S3.
Figure 4.2 ETERNUS DX8700 S3/DX8900 S3 setup (Setup Power Management screen)
•
Auto Power
Select "Disable".
•
Power Resume
Select "Disable".
•
Connection SVC
Select the SVCs (SVC#0 and/or SVC#1) of the ETERNUS DX8700 S3/DX8900 S3 that are connected to the
power synchronized unit with the RS232C cable.
Select "SVC#0" when the power synchronized unit is connected to the PWC port on SVC#0. Select "SVC#1"
when the power synchronized unit is connected to the PWC port on SVC#1.
When different power synchronized units are connected to SVC#0 and SVC#1 in a duplicated configuration,
select both "SVC#0" and "SVC#1".
•
Delay until Shutdown
Do not change the default setting (0 minute).
•
Set management unit interface
Select "Power Synchronized Unit".
•
Power Failure Signal
"Positive" (positive logic) is automatically set.
•
Low Battery Signal
"Negative" (negative logic) is automatically set.
•
UPS Shutdown Signal
Do not select the "Enable" checkbox.
"Positive" (positive logic) is set by default.
FUJITSU Storage ETERNUS DX, ETERNUS AF Configuration Guide (Power Synchronized Unit)
47
Copyright 2017 FUJITSU LIMITED
P3AM-8012-10ENZ0