APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 38 of 52)
ADDR
REGISTER NAME
B242
...Repeated for Received Analog 26
B244
...Repeated for Received Analog 27
B246
...Repeated for Received Analog 28
B248
...Repeated for Received Analog 29
B24A
...Repeated for Received Analog 30
B24C
...Repeated for Received Analog 31
B24E
...Repeated for Received Analog 32
IEC 61850 Report Settings (Read/Write Setting) (16 modules)
B280
IEC 61850 Report Control 1 RptID
B2A1
IEC 61850 Report Control 1 OptFlds
B2A2
IEC 61850 Report Control 1 BufTm
B2A4
IEC 61850 Report Control 1 TrgOps
B2A5
IEC 61850 Report Control 1 IntgPd
B2A7
...Repeated for Report 2
B2CE
...Repeated for Report 3
B2F5
...Repeated for Report 4
B31C
...Repeated for Report 5
B343
...Repeated for Report 6
B36A
...Repeated for Report 7
B391
...Repeated for Report 8
B3B8
...Repeated for Report 9
B3DF
...Repeated for Report 10
B406
...Repeated for Report 11
B42D
...Repeated for Report 12
B454
...Repeated for Report 13
B47B
...Repeated for Report 14
B4A2
...Repeated for Report 15
B4C9
...Repeated for Report 16
IEC 61850 GGIO1 Configuration Settings (Read/Write Setting)
B500
Number of Status Indications in GGIO1
B501
IEC 61850 GGIO1 Indication FlexLogic Operands (128
items)
IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 modules)
B5A0
IEC 61850 Configurable GOOSE Function (GoEna)
B5A1
IEC 61850 Configurable GOOSE ID
B5C2
Configurable GOOSE Destination MAC Address
B5C5
IEC 61850 Configurable GOOSE VLAN Transmit Priority
B5C6
IEC 61850 Configurable GOOSE VLAN ID
B5C7
IEC 61850 Configurable GOOSE ETYPE APPID
B5C8
IEC 61850 Configurable GOOSE ConfRev (Configuration
Revision)
B5CA
IEC 61850 Configurable GOOSE Retransmission Curve
B5CB
Configurable GOOSE Dataset Items for Transmission
(64 items)
B60B
...Repeated for Module 2
B676
...Repeated for Module 3
B6E1
...Repeated for Module 4
B74C
...Repeated for Module 5
B7B7
...Repeated for Module 6
B822
...Repeated for Module 7
B88D
...Repeated for Module 8
IEC 61850 Configurable GOOSE Reception (Read/Write Setting) (8 modules)
B900
IEC 61850 Configurable GOOSE Dataset Items for
Transmission (64 items)
B940
...Repeated for Module 2
GE Multilin
RANGE
---
0 to 65535
0 to 4294967295
0 to 65535
0 to 4294967295
8 to 128
---
0 to 1
---
---
0 to 7
0 to 4095
0 to 16383
1 to 4294967295
0 to 3
0 to 542
0 to 197
B30 Bus Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
---
F209
---
1
F001
---
1
F003
---
1
F001
---
1
F003
---
8
F001
---
---
F300
---
1
F102
---
---
F209
"GOOSEOut_x_"
---
---
F072
---
1
F001
---
1
F001
---
1
F001
---
1
F003
---
1
F611
---
1
F232
---
1
F233
DEFAULT
B
(none)
0
0
0
0
8
0
1 (Enabled)
0
4
0
0
1
3 (Relaxed)
0 (None)
0 (None)
B-45