TARGETS MENU
7.2.2.2 Major self-test error messages
The major self-test errors are outlined in this section.
INCOMPATIBLE H/W:
Contact Factory (xxx)
•
Latched target message: Yes.
•
Description of problem: One or more installed hardware modules is not compatible with the L30 order code.
•
How often the test is performed: Module dependent.
•
What to do: Contact the factory and supply the failure code noted in the display. The "xxx" text identifies the failed
module (for example, F8L).
EQUIPMENT MISMATCH:
with 2nd line detail
•
Latched target message: No.
•
Description of problem: The number or type of installed hardware modules does not match the order code stored in
the L30.
•
How often the test is performed: On power up. Afterwards, the backplane is checked for missing cards every five
seconds.
•
What to do: Check all modules against the order code, ensure they are inserted properly, and cycle control power. If a
module has intentionally been added or removed, refresh the order code under Device Setup. If the problem persists,
contact the factory.
FLEXLOGIC ERROR:
with 2nd line detail
•
Latched target message: No.
•
Description of problem: A FlexLogic equation is incorrect.
•
How often the test is performed: The test is event driven, performed whenever FlexLogic equations are modified
•
What to do: Finish all equation editing and use self tests to debug any errors.
UNIT NOT PROGRAMMED:
Check Settings
•
Latched target message: No.
7
•
Description of problem: The
programmed.
•
How often the test is performed: On power up and whenever the
setting is altered
•
What to do: Program all settings and then set
DIAGNOSTIC FAILURE___:
Self Test Error
•
Latched target message: No.
•
Description of problem: Internal recovery failure detected.
•
How often the test is performed: Continuous.
•
What to do: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
SYSTEM FAILURE___:
with 2nd line detail
7-8
PRODUCT SETUP INSTALLATION RELAY SETTINGS
.
PRODUCT SETUP INSTALLATION RELAY SETTINGS
PRODUCT SETUP INSTALLATION RELAY SETTINGS
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: COMMANDS AND TARGETS
setting indicates the L30 is not