Synchrocheck - GE D30 Instruction Manual

Line distance
Hide thumbs Also See for D30:
Table of Contents

Advertisement

5.6 CONTROL ELEMENTS
SETTINGS
SELECTOR 1 FUNCTION:
5
Enabled = 1
SELECTOR 1 STEP-UP:
Off = 0
SELECTOR 1 ACK:
Off = 0
SELECTOR 1 3BIT A0:
Off = 0
SELECTOR 1 3BIT A1:
Off = 0
SELECTOR 1 3BIT A2:
Off = 0
SELECTOR 1 3BIT ACK:
Off = 0
PATH: SETTINGS
CONTROL ELEMENTS

SYNCHROCHECK 1

5-154
SETTINGS
SELECTOR 1 FULL RANGE:
SELECTOR 1 STEP-UP MODE:
SELECTOR 1 3BIT MODE:
SELECTOR 1 TIME-OUT:
SELECTOR 1 POWER-UP MODE:
RUN
step up
acknowledge
3-bit acknowledge
Figure 5–88: SELECTOR SWITCH LOGIC
SYNCHROCHECK
SYNCHK1 FUNCTION:
Disabled
SYNCHK1 BLOCK:
MESSAGE
Off
SYNCHK1 V1 SOURCE:
MESSAGE
SRC 1
SYNCHK1 V2 SOURCE:
MESSAGE
SRC 2
SYNCHK1 MAX VOLT
MESSAGE
DIFF: 10000 V
SYNCHK1 MAX ANGLE
MESSAGE
DIFF:
30°
SYNCHK1 MAX FREQ
MESSAGE
DIFF: 1.00 Hz
SYNCHK1 MAX FREQ
MESSAGE
HYSTERESIS: 0.06 Hz
SYNCHK1 DEAD SOURCE
MESSAGE
SELECT: LV1 and DV2
SYNCHK1 DEAD V1
MESSAGE
MAX VOLT: 0.30 pu
SYNCHK1 DEAD V2
MESSAGE
MAX VOLT: 0.30 pu
D30 Line Distance Relay
ACTUAL VALUE
SELECTOR 1 POSITION
FLEXLOGIC™ OPERANDS
SELECTOR 1 POS 1
2
1
SELECTOR 1 POS 2
3
SELECTOR 1 POS 3
4
SELECTOR 1 POS 4
SELECTOR 1 POS 5
ON
7
5
SELECTOR 1 POS 6
6
SELECTOR 1 POS 7
FLEXLOGIC™ OPERANDS
SELECTOR 1 STP ALARM
SELECTOR 1 BIT ALARM
3-bit position out
SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
SYNCHROCHECK 1(2)
Range: Disabled, Enabled
Range: FlexLogic™ operand
Range: SRC 1, SRC 2
Range: SRC 1, SRC 2
Range: 0 to 400000 V in steps of 1
Range: 0 to 100° in steps of 1
Range: 0.00 to 2.00 Hz in steps of 0.01
Range: 0.00 to 0.10 Hz in steps of 0.01
Range: None, LV1 and DV2, DV1 and LV2, DV1 or DV2,
DV1 Xor DV2, DV1 and DV2
Range: 0.00 to 1.25 pu in steps of 0.01
Range: 0.00 to 1.25 pu in steps of 0.01
5 SETTINGS
842012A2.CDR
5.6.4 SYNCHROCHECK
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents