AUTOMATION LOGIC
470
Figure 416: Remote voltage magnitude calculation logic
Now that the remote voltage magnitude has been calculated, the following logic
calculates the voltage difference between this and the setting voltage.
Figure 417: Voltage difference automation logic
The current on each phase is checked to ensure that it is less than the maximum allowable
for a tap changer operation.
Figure 418: Overcurrent check automation logic
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 8: AUTOMATION