CHAPTER 3: DNP COMMUNICATION

DNP v3.00 implementation document

Object 1 (binary inputs)
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Explanation of sometimes — Object 12 points are mapped to the D90
The persistence of virtual inputs is determined by the virtual input Type settings. The
"Pulse on" and "Latch on" operations perform the same function in the D90
the appropriate virtual input is placed in the "On" state. If the virtual input is
programmed to "Self-Reset," it resets after one FlexLogic™ pass. The on/off times and
count value are ignored. The "Pulse off" and "Latch off" operations place the
appropriate virtual input into the "Off" state. The "Trip" and "Close" operations place
the appropriate virtual input into the "On" state.
Reports binary input change events when no specific variation requested — Only
time-tagged
Reports time-tagged binary input change events when no specific variation requested
— Binary input change with time
Sends unsolicited responses — Configurable; enable/disable unsolicited function
codes supported
Sends static data in unsolicited responses — Never
Default counter object/variation:
Default object — 20
Default variation — 1
A point-by-point list is attached.
Counters roll over at:
16 bits (counter 8)
32 bits (counters 0 to 7 and 9)
A point-by-point list is attached.
Sends multi-fragment responses — Yes
This section identifies the variations, function codes, and qualifiers supported by the
Plus
D90
in both request and response messages. For static (non-change-event) objects,
requests sent with qualifiers 00, 01, 06, 07, or 08, are responded to with qualifiers 00 or 01.
Static object requests sent with qualifiers 17 or 28 are responded to with qualifiers 17 or
28. For change-event objects, qualifiers 17 or 28 are always responded to.
A default variation refers to the variation responded when variation 0 is requested and in
class 0, 1, 2, or 3 scans. The default variations for object types 1, 2, 20, 21, 22, 23, 30, and 32
Plus
are selected via the D90
For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a
request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests sent
with qualifiers 00, 01, 06, 07, or 08 are responded to with qualifiers 00 or 01 (for change-
event objects, qualifiers 17 or 28 are always responded to).
Cold restarts are implemented the same as warm restarts, meaning when the DNP process
Plus
restarts, not the D90
.
Object 1, Variation 0: Binary input (default variation)
Variation 0 is used to request the default variation. The following codes are used for
requests.
Function codes for requests, object 1, variation 0:
1 (read)
22 (assign class)
settings. This optimizes the class 0 poll data size.
DNP DEVICE PROFILE
Plus
virtual inputs.
Plus
; that is,
199