3.2 Applying Power to the Frequency Converter

WARNING
HIGH VOLTAGE!
Frequency converters contain high voltage when
connected to AC mains. Installation, start-up and
maintenance should be performed by qualified personnel
only. Failure to perform installation, start-up and
maintenance by qualified personnel could result in death
or serious injury.
WARNING
UNINTENDED START!
When frequency converter is connected to AC mains, the
motor may start at any time. The drive, motor, and any
driven equipment must be in operational readiness. Failure
to be in operational readiness when the drive is connected
to AC mains could result in death, serious injury,
equipment, or property damage.
1.
Confirm input voltage is balanced within 3%. If
not, correct input voltage imbalance before
proceeding. Repeat procedure after voltage
correction.
2.
Ensure optional equipment wiring, if present,
matches installation application.
3.
Ensure that all operator devices are in the OFF
position. Panel doors closed or cover mounted.
4.
Apply power to the unit. DO NOT start the drive
at this time. For units with a disconnect switch,
turn to the ON position to apply power to the
drive.

3.3 Basic Operational Programming

Frequency converters require basic operational
programming prior to running for best performance. Basic
operational programming requires entering motor-
nameplate data for the motor being operated and the
minimum and maximum motor speeds. Enter data in
accordance with the following procedure. Parameter
settings recommended are intended for start up and
checkout purposes. Application settings may vary. See
4 User Interface for detailed instructions on entering data
through the Keypad.
Enter data with power ON, but prior to operating the
frequency converter.
1.
Press [Quick Menu] on the Keypad.
2.
Use the navigation keys to scroll to Quick Start
and press [OK].
AF-650 GP Operating Instructions
3.
4.
5.
6.
7.
8.
9.
10.
11.
This concludes the quick set-up procedure. Press [Status]
to return to the operational display.
Select language and press [OK]. Then enter the
motor data in parameters P-02, P-03, P-06, P-07,
F-04 and F-05. The information can be found on
the motor nameplate.
P-07 Motor Power [kW] or P-02 Motor
Power [HP]
F-05 Motor Rated Voltage
F-04 Base Frequency
P-03 Motor Current
P-06 Base Speed
Enter F-01 Frequency Setting 1 and press [OK].
Enter F-02 Operation Method. Local, Remote, or
Linked to Hand/Auto. In local the reference is
entered on the keypad, and in remote that
reference is sourced depending on .
Enter the accel/decel time in F-07 Accel Time 1
and F-08 Decel Time 1.
For F-10 Electronic Overload enter Elec OL Trip 1
for Class 20 overload protection. For further
information, please see 2.4.1 Requirements.
For F-17 Motor Speed High Limit [RPM] or
F-15 Motor Speed High Limit [Hz] enter the
application requirements.
For F-18 Motor Speed Low Limit [RPM] or
F-16 Motor Speed Low Limit [Hz] enter the
application requirements.
Set H-08 Reverse Lock to Clockwise, Counter
clockwise or Both directions.
In P-04 Auto Tune select Reduced Auto Tune or
Full Auto Tune and follow on-screen instructions.
See 3.4 Auto Tune
3
3
23