CHAPTER 3: INTERFACES
NOTE:
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Self-test Error
Description of Problem How Often the Test is
1
Message
Traffic Error
Abnormally high
Primary
amount of Broadcast
and Uni-cast traffic on
port 1 or port 4
Traffic Error
Abnormally high
Secondary
amount of Broadcast
and Uni-cast traffic on
port 5
Ambient
The ambient
Temperature >80C
temperature
surrounding the
product has exceeded
80C
Event Rate High
Abnormally high
amounts of events
have been generated
so the relay has
stopped logging to
prevent further issues
IRIG-B Failure
A bad IRIG-B input
signal has been
detected
Version Mismatch
CPU and Comms do not
have the same revision
on firmware
SelfTestFWUpdate The updating of the
firmware failed
Remote CAN IO
The value of the cards
Mismatch
in the slots detected by
the Remote IO does not
match the value
validated by the user
configuration
1. – Failure is logged after the detection of 5 consecutive failures
2. $ – is the slot ID (i.e., F, G, H etc.)
3.To disable Link Error Primary target when not in-use with SE order code, change IP
address to 127.0.0.1
Table 3-8: Major Self-test Errors
Self-test Error
Latched
Message
Target
Message
Relay Not
No
Ready
Major Self-Test
Yes
(error code)
When a total loss of power is present, the Critical Failure Relay (Output Relay 8) is de-
energized.
Performed
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Boot-up and Every 1
second
Every 1 second
Every 1 second. A
failure is declared after
60 consecutive failures
Description of
How Often the Test
Problem
is Performed
PRODUCT SETUP
On power up and
INSTALLATION
whenever the
setting indicates
PRODUCT SETUP
relay is not in a
INSTALLATION
programmed state.
setting is altered.
Unit hardware failure
Every 1 second
detected
FRONT CONTROL PANEL INTERFACE
What to do
Contact site IT department to
check network for
malfunctioning devices
Contact site IT department to
check network for
malfunctioning devices
Inspect mounting enclosure
for unexpected heat sources
(i.e loose primary cables) and
remove accordingly
Ensure settings are not set
close to nominal ratings.
Ensure Flexlogic equations
do not have impractical
timing for status events
Ensure IRIG-B cable is
connected, check cable
functionality (i.e. physical
damage or perform
continuity test), ensure IRIG-
B receiver is functioning, and
check input signal level (it
may be less than
specification). If none of
these apply, contact the
factory.
Ensure that both the CPU
and Comms FW was
uploaded during the
upgrade process
Re-try uploading firmware. If
the upload doesn't work a
second time contact factory
Fix the remote CANBUS IO
mismatch.
What to do
Program all required
settings and then set the
PRODUCT SETUP
INSTALLATION setting to
"Ready".
Contact the factory and
supply the failure code as
noted on the display.
3–13