Planning Notes - Bosch FAP-O 500 Series Product Information

Lsn fire detectors
Table of Contents

Advertisement

Product Information 500 Series LSN Fire Detectors (EU)

2. Planning Notes

The 500 series detectors are approved for indoor use only!
The detectors must be installed exclusively in the FAA−500 bases
provided. In addition, the detector base must be installed in an
FAA−500−BB ceiling mount back box or in an FAA−500−SB surface
mount back box.
D Country−specific standards and guidelines must be observed during the planning
phase.
D The FAP−OC 500, like the FAP−O 500, is planned according to the guidelines for
optical detectors; see DIN VDE 0833 Part 2 and VdS 2095.
D A hemispherical space (see Fig. 3., Pos. 2)
with a radius of 50 cm must remain free
below the detector (Pos. 1).
Care must be taken to ensure that no peo-
ple, larger animals, plants, opening doors
or any objects intrude into this area and
that no parts of the detector surface be-
come covered.
D The detector may only be installed in a position which is out of arm's reach.
Minimum installation height recommended by BOSCH: 2.70 m.
D The 500 series detectors may not be installed in rooms with data transmission by
means of high−intensity infra−red light (e.g. in rooms with IR systems for interpreters).
D The detectors must be mounted so that they are not exposed to any direct sunlight.
D A minimum distance of 50 cm from lamps must be maintained.
The detectors may not be mounted in a cone of light from lamps.
D The standard spring inside the bases allows detector mounting in false ceiling
panels. For concrete and wooden ceiling, replace with the FAA−500−SPRING with
red marking (ordering information see section 6.2.).
D Maximum permitted air speed: 20
D Maximum number of FAP−500 detectors connectable to the Local SecurityNetwork
LSN:
− BOSCH LSN fire panels: up to 28 detectors per NVU as loop or stub line
− Modular Fire Panel FPA−5000: up to 85 detectors per LSN 0300−Modul.
Ï Ï Ï Ï Ï Ï Ï Ï Ï Ï Ï
Ï Ï Ï Ï Ï Ï Ï Ï Ï Ï Ï
Ï Ï Ï Ï Ï Ï Ï Ï Ï Ï Ï
Ï Ï Ï Ï Ï Ï Ï Ï Ï Ï Ï
Ï Ï Ï Ï Ï Ï Ï Ï Ï Ï Ï
3.
m
/
.
s
Page 11
PI − 34.70 en
1
2
BDL−F.01U.025.876
A5.en/ 02.02.2006
ST−FIR/PRM1 / zab

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fap-o 500-p seriesFap-oc 500seriesFap-oc 500-p series

Table of Contents