Specifications
Digital inputs:
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, R
i
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
Analog inputs:
Number of analog inputs
Terminal number
Modes
Mode select
Voltage mode
Voltage level
Input resistance, R
i
Max. voltage
Current mode
Current level
Input resistance, R
i
Max. current
Resolution for analog inputs
Accuracy of analog inputs
Bandwidth
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Pulse inputs:
Programmable pulse inputs
Terminal number pulse
Max. frequency at terminal, 29, 33
Max. frequency at terminal, 29, 33
Min. frequency at terminal 29, 33
Voltage level
Maximum voltage on input
Input resistance, R
i
Pulse input accuracy (0.1–1 kHz)
Analog output:
Number of programmable analog outputs
Terminal number
Current range at analog output
AF-600 FP Quick Guide
DET-759A
4 (6)
1)
18, 19, 27
, 29, 32, 33,
PNP or NPN
0–24V DC
< 5V DC
> 10V DC
> 19 V DC
< 14V DC
28V DC
approx. 4kΩ
2
53, 54
Voltage or current
Switches A53 and A54
Switch A53/A54 = (U)
0 to + 10 V (scaleable)
approx. 10 kΩ
± 20 V
Switch A53/A54 = (I)
0/4 to 20 mA (scaleable)
approx. 200 Ω
30 mA
10 bit (+ sign)
Max. error 0.5% of full scale
200 Hz
2
29, 33
110 kHz (push-pull driven)
5 kHz (open collector)
4 Hz
see section on Digital input
28 V DC
approx. 4 kΩ
Max. error: 0.1% of full scale
1
42
0/4 - 20 mA
33
8
8

Advertisement

loading