GE D30 Instruction Manual page 464

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

PHASE DISTANCE APPLIED TO POWER TRANSFORMERS
Table 9-9: Phase distance input signals for delta-wye transformers
Transformer
connection
None
Dy1
Dy3
9
9-12
Figure 9-4: Applications of the "PHS DIST XF MR VOL/CUR CONNECTION" settings
(a)
delta
wye, 330
Z3
Z3 XFRM VOL CONNECTION = None
Z3 XFRM CUR CONNECTION = None
Z1
Z1 XFRM VOL CONNECTION = Dy11
Z1 XFRM CUR CONNECTION = Dy11
(c)
delta
wye, 330
Z3
Z3 XFRM VOL CONNECTION = None
Z3 XFRM CUR CONNECTION = Yd1
Z1
Z1 XFRM VOL CONNECTION = Dy11
Z1 XFRM CUR CONNECTION = None
Loop
Current transformation
I
I
AB
A
B
I
I
BC
B
C
I
I
CA
C
A
3I
AB
A
3I
BC
B
3I
CA
C
I
=
3I
AB
AB_21P
I
=
3I
BC
BC_21P
I
=
3I
CA
CA_21P
(b)
o
lag
Z3 XFRM VOL CONNECTION = Yd1
Z3 XFRM CUR CONNECTION = None
Z1 XFRM VOL CONNECTION = None
Z1 XFRM CUR CONNECTION = Dy11
(e)
o
lag
L
1
Zone 3
Z
L1
Voltage transformation
V
AB
V
BC
V
CA
1
----- - V
(
V
AB
CA
3
1
----- - V
(
V
BC
AB
3
1
(
----- - V
V
CA
BC
3
1
C
V
=
----- - V
AB_21P
1
A
V
=
----- - V
BC_21P
1
B
V
=
----- - V
CA_21P
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 9: THEORY OF OPERATION
o
delta
wye, 330
lag
Z3
Z1
L
2
Zone 1
Z
Z
T
L2
830717A1.CDR
)
)
)
(
V
)
BC
CA
3
(
V
)
CA
AB
3
(
V
)
AB
BC
3