GE Reason RT430 Technical Manual page 43

A clock referenced to gps and glonass satellites
Hide thumbs Also See for Reason RT430:
Table of Contents

Advertisement

IEC 61000-4-17:1999
IEC 61000-4-18:2006
Gradual Startup
CISPR11:2009
CISPR22:2008
TABLE 23: Safety tests
Safety
IEC 60255-5
RT430-TM-EN-5
Test level: 15 % of rated d.c. value
Test frequency: 120Hz, sinusoidal waveform.
Voltage oscillation frequency: 1MHz
Differential mode: 1kV peak voltage;
Common mode 2,5kV peak voltage
Shut-down ramp: 60s
Power off: 5m
Start-up ramp: 60s
Radiated emission
Limits:
30 to 230MHz - 50dB(μV/m) quasi peak at 3m
230 to 1000MHz - 57dB(μV/m) quasi peak at 3m
Radiated emission
The definition of the limit frequency is based on the maximum internal
frequency of the equipment. On RT430, the maximum internal frequency
is 100 MHz. For this case, the levels of CISPR 11 satisfy the normative
IEC 60255-26.
Conducted emission
Limits:
0.15 to 0.50MHZ - 79dB(μV) quasi peak; 66dB(μV) average
0.5 to 30MHz - 73dB(μV) quasi peak; 60dB(μV) average
IEC 61010-1
Inpulse - 5KV
Dielectric withstand - 3,3KVDC
Ω
Insulation > 100M