Snmp Settings Screen - HP UPS Network Module User Manual

Table of Contents

Advertisement

0 to 99999 seconds, 30 seconds by default). This option allows utility power to stabilize and
disks in shared storage configurations to spin up before the server restarts.
Click Save.
2.
For detailed information about configuring the shutdown parameters, see "Shutdown parameters (on page
52)."
Click Help to view online help.

SNMP Settings screen

Click SNMP in the menu tree to display the SNMP Settings screen. This screen allows an administrator to
configure SNMP settings for computers that use the HP Power MIB to request information from the UPS
Network Module.
To configure the SNMP settings:
Select the SNMP version supported by the UPS Network Module from the Version pull-down menu.
1.
Available options are Disabled, V1, V3, and V1 and V3.
Configure the SNMP V1 settings:
2.
Enter the SNMP Community Read-Only string. The UPS Network Module and the Clients must share
a.
the same community name to communicate.
Select or clear the SNMP Write Enabled checkbox to enable or disable the SNMP write function.
b.
If the SNMP write function is enabled, enter the SNMP Community Write string. The UPS Network
c.
Module and the Clients must share the same community name to communicate.
Configure the SNMP V3 settings:
3.
Enter a user name for the Read-Only User. This user is only authorized to read SNMP variables.
a.
Select a level of security from the Read-Only Security Level pull-down menu:
b.
No Auth No Priv—The user does not use authentication and privacy to access SNMP variables.
HP UPS Network Module web interface 39