Design Parameters - York YCAL0014 User Manual

Air-cooled scroll chillers style c, 13-130 ton, 46-456 kw, 60 hz
Table of Contents

Advertisement

Design Parameters

YCAL
TEMPERATURE (°F)
MIN
0014*
40
0020*
40
0024*
40
000*
40
004*
40
0040*
40
0042*
40
0044*
40
0050*
40
0060*
40
0064*
40
0070*
40
0074
40
000
40
000
40
004
40
0104
40
0114
40
0124
40
014
40
* Available in HFC-407c only.
YCAL
TEMPERATURE (°C)
MIN
0014*
4.4
0020*
4.4
0024*
4.4
000*
4.4
004*
4.4
0040*
4.4
0042*
4.4
0044*
4.4
0050*
4.4
0060*
4.4
0064*
4.4
0070*
4.4
0074
4.4
000
4.4
000
4.4
004
4.4
0104
4.4
0114
4.4
0124
4.4
014
4.4
* Available in HFC-407c only.
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK Office for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK Office for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
4. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed on the system (for YCAL0014-
0080 models only).
5. For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.
JOHNSON CONTROLS
ENGLISH UNITS
1
MAX
2
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
1
MAX
2
12.8
12.8
12.8
12.8
12.8
12.8
12.8
12.8
12.8
12.8
12.8
12.8
12.8
12.8
12.8
12.8
12.8
12.8
12.8
12.8
LEAVING WATER

COOLER FLOW (GPM
)
MIN
MAX
25
60
25
60
30
70
35
170
35
170
60
325
60
325
60
325
60
325
60
325
100
350
100
350
100
350
100
400
138
525
138
525
156
625
156
625
156
625
156
625
SI UNITS
LEAVING WATER

COOLER FLOW (l/s
)
MIN
MAX
1.6
3.8
1.6
3.8
1.9
4.4
2.2
10.7
2.2
10.7
3.8
20.5
3.8
20.5
3.8
20.5
3.8
20.5
3.8
20.5
6.3
22.1
6.3
22.1
6.3
22.1
6.3
25.2
8.7
33.1
8.7
33.1
9.8
39.4
9.8
39.4
9.8
39.4
9.8
39.4
FORM 150.62-EG1 (507)
AIR ON CONDENSER (°F)
MIN
4
MAX
5
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
AIR ON CONDENSER (°C)
MIN
4
MAX
5
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
1

Hide quick links: