Air-cooled scroll chillers style c, 13-130 ton, 46-456 kw, 60 hz

Advertisement

FORM 150.62-EG1 (507)
AIR-COOLED
SCROLL CHILLERS
STYLE C
YCAL0014 – YCAL0134
13 – 130 TON
46 – 456 kW
60 Hz
R-22
R-407C
on select models only
on all models

Advertisement

Table of Contents
loading

Summary of Contents for York YCAL0014

  • Page 1 FORM 150.62-EG1 (507) AIR-COOLED SCROLL CHILLERS STYLE C YCAL0014 – YCAL0134 13 – 130 TON 46 – 456 kW 60 Hz R-22 R-407C on select models only on all models...
  • Page 2: Table Of Contents

    Part Load Ratings - R-407C (SI Units)................................42 Physical Data - (English Units)..................................44 Physical Data - (SI Units)....................................46 Dimensions - YCAL0014-YCAL0020 (English)..............................48 Dimensions - YCAL0024-YCAL0034 (English)..............................50 Dimensions - YCAL0040-YCAL0060 (English)..............................52 Dimensions - YCAL0064-YCAL0080 (English).
  • Page 3: Introduction

    FORM 150.62-EG1 (507) Introduction YORK Millennium ® Air-Cooled Scroll Chillers provide chilled water for all air conditioning appli- cations using central station air handling or terminal units. They are completely self-contained and are designed for outdoor (roof or ground level) installation. Each unit includes hermetic scroll compressors, a liquid cooler, air cooled condenser, and a weather resistant microprocessor control center, all mounted on a formed steel base.
  • Page 4: Specification

    Specification The cooler is covered with 3/4" flexible, closed-cell, foam GENERAL insulation (K=0.25). The 10 - 135 Ton (35 - 475 kW) YCAL models are shipped complete from the factory ready for installation The water baffles are constructed of galvanized steel to and use.
  • Page 5 Ambient temperature • Discharge pressure (optional) System pressures (each circuit) • Liquid Temperature Reset via a YORK ISN DDC or Operating hours and starts (each compressor) Building Automation System (by others) via: Print calls up to the liquid crystal display:...
  • Page 6 Provisions are included for: pumpdown at shutdown; POWER PANEL optional remote chilled water temperature reset and two steps of demand load limiting from an external building Each panel contains: automation system. Unit alarm contacts are standard. • Compressor power terminals •...
  • Page 7: Options And Accessories

    (in - (The standard control panel can be directly connected compliance with Article 440-14 of N.E.C.) to isolate to a YORK Building Automated System via the stan- unit power voltage for servicing. Factory intercon- dard on-board RS485 communication port.) necting wiring is provided from the disconnect switch to factory supplied system circuit breakers.
  • Page 8 This option also includes a system high pressure nitrogen holding charge. Interconnecting rigid piping, wiring relief valve in compliance with ASHRAE 15. (Factory- and refrigerant are by others. Includes YORK Service start- mounted.) up. See Form 150.62-NM1.1 (200) for other application information.
  • Page 9 Additionally, for proper head pres- VIBRATION ISOLATORS – Level adjusting, spring type 1" sure control, YORK recommends the use of Condenser (25.4mm) or seismic deflection or neoprene pad isolators Louvered Panels for winter applications where wind gustss may exceed five miles per hour.
  • Page 10 This page intentionally left blank. JOHNSON CONTROLS...
  • Page 11: Selection Data

    For ETHYLENE GLYCOL unusual applications or uses beyond the scope of this TONS PRESS COMPR F/TON % WEIGHT FREEZE PT catalog, please consult your nearest YORK Office or ° DROP representative. 0.985 0.997 24.1 1.034 0.981 0.996...
  • Page 12 3. From the Ratings on pages 16 - 46: 5. From RATINGS on pages 16 - 46: SELECT: YCAL0050 (English Units) SELECT: YCAL0040 (English Units) 53.1 Tons 36.1 Tons 48.7 Compressor kW 38.6 Compressor kW 11.7 Unit EER 4. Calculate Compressor kW at 50 Tons: 6.
  • Page 13: Design Parameters

    3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard. 4. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed on the system (for YCAL0014- 0080 models only).
  • Page 14: Water Pressure Drop

    Water Pressure Drop ENGLISH 100.0 10.0 1000 Flow, GPM MODEL YCAL COOLER CURVE 0014, 0020 0024 000, 004 0040, 0042 0044, 0050, 0060 0064, 0070, 0074 000 000, 004 0104, 0114, 0124, 014 Note: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges. See page 13 for minimum and maximum flow points.
  • Page 15 FORM 150.62-EG1 (507) 1000.0 100.0 10.0 10.0 100.0 Flow, L/S MODEL YCAL COOLER CURVE 0014, 0020 0024 000, 004 0040, 0042 0044, 0050, 0060 0064, 0070, 0074 000 000, 004 0104, 0114, 014 Note: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges. See page 13 for minimum and maximum flow points.
  • Page 16: Ratings - R-22 (English Units)

    Ratings - R-22 (English Units) IPLV=14.4 YCAL0074EC AIR TEMPERATURE ON CONDENSER (°F) 75°F 80°F 85°F 90°F 95°F 100°F LCWT (°F) TONS EER TONS EER TONS EER TONS EER TONS EER TONS 78.3 68.1 12.5 76.6 71.9 11.7 74.7 76.0 10.8 72.9 80.4 10.0...
  • Page 17 FORM 150.62-EG1 (507) IPLV=14.4 YCAL0074EC AIR TEMPERATURE ON CONDENSER (°F) 105°F 110°F 115°F 120°F 125°F LCWT (°F) TONS EER TONS EER TONS EER TONS EER TONS 66.9 95.0 64.7 100.4 62.6 106.0 50.6 87.4 40.9 72.2 40.0 69.3 95.8 67.1 101.2 64.8 106.8...
  • Page 18 Ratings - R-22 (English Units) IPLV=14.0 YCAL0104EC AIR TEMPERATURE ON CONDENSER (°F) 75°F 80°F 85°F 90°F 95°F 100°F LCWT (°F) TONS EER TONS EER TONS EER TONS EER TONS EER TONS 102.6 88.5 12.4 100.3 93.1 11.6 97.9 97.9 10.8 95.5 103.1 10.1...
  • Page 19 FORM 150.62-EG1 (507) YCAL0104EC IPLV=14.0 AIR TEMPERATURE ON CONDENSER (°F) 105°F 110°F 115°F 120°F 125°F LCWT (°F) TONS EER TONS EER TONS EER TONS EER TONS 87.8 120.9 85.2 127.7 82.4 134.9 79.6 142.5 64.7 116.1 40.0 91.0 122.1 88.2 128.9 85.4 136.2...
  • Page 20: Ratings - R-22 (Si Units)

    Ratings - R-22 (SI Units) COP=4.22 YCAL0074EC AIR TEMPERATURE ON - CONDENSER (°C) 25°C 30°C 35°C 40°C 45°C 50°C LCWT (°C) 277.7 69.9 266.1 77.2 253.7 85.4 240.9 94.3 227.0 104.1 149.8 70.1 286.2 70.5 274.3 77.8 261.7 86.0 248.5 95.0 234.3 104.8...
  • Page 21 FORM 150.62-EG1 (507) YCAL0104EC COP=4.12 AIR TEMPERATURE ON - CONDENSER (°C) LCWT 25°C 30°C 35°C 40°C 45°C 50°C (°C) 363.3 90.8 348.5 99.5 332.7 109.2 316.2 120.2 299.1 132.6 236.5 112.9 375.3 91.8 359.4 100.4 343.2 110.2 326.3 121.3 308.7 133.7 244.3 113.7...
  • Page 22: Ratings - R-407C (English Units)

    Ratings - R-407C (English Units) IPLV=12.6 YCAL0014EB AIR TEMPERATURE ON CONDENSER (°F) 75°F 80°F 85°F 90°F 95°F 100°F LCWT (°F) TONS EER TONS EER TONS EER TONS EER TONS EER TONS 13.4 11.2 11.4 13.0 11.9 10.6 12.6 12.7 12.3 13.5 11.7 14.7...
  • Page 23 FORM 150.62-EG1 (507) YCAL0014EB IPLV=12.6 AIR TEMPERATURE ON CONDENSER (°F) 105°F 110°F 115°F 120°F 125°F LCWT (°F) TONS EER TONS EER TONS EER TONS EER TONS 11.1 16.1 10.7 17.1 10.3 18.1 40.0 11.3 16.6 11.1 17.1 10.7 18.1 42.0 11.8 16.6 11.4...
  • Page 24 Ratings - R-407C (English Units) YCAL004EB IPLV=14.1 AIR TEMPERATURE ON CONDENSER (°F) 75°F 80°F 85°F 90°F 95°F 100°F LCWT (°F) TONS EER TONS EER TONS EER TONS EER TONS EER TONS 33.3 31.6 11.6 32.4 33.6 10.7 31.4 35.6 30.4 37.7 29.4 40.0...
  • Page 25 FORM 150.62-EG1 (507) YCAL004EB IPLV=14.1 AIR TEMPERATURE ON CONDENSER (°F) 105°F 110°F 115°F 120°F 125°F LCWT (°F) TONS EER TONS EER TONS EER TONS EER TONS 27.4 44.7 26.4 47.2 25.4 49.7 17.2 32.6 16.5 34.3 40.0 28.5 45.1 27.4 47.6 26.4 50.1...
  • Page 26 Ratings - R-407C (English Units) YCAL0050EB IPLV=13.7 AIR TEMPERATURE ON CONDENSER (°F) 75°F 80°F 85°F 90°F 95°F 100°F LCWT (°F) TONS EER TONS EER TONS EER TONS EER TONS EER TONS 50.3 47.4 11.4 48.9 50.3 10.5 47.5 53.3 46.1 56.5 44.7 59.9...
  • Page 27 FORM 150.62-EG1 (507) YCAL0050EB IPLV=13.7 AIR TEMPERATURE ON CONDENSER (°F) 105°F 110°F 115°F 120°F 125°F LCWT (°F) TONS EER TONS EER TONS EER TONS EER TONS 41.7 67.3 40.2 71.2 29.2 51.4 20.2 35.3 19.4 37.4 40.0 43.4 67.7 41.8 71.7 30.2 52.1...
  • Page 28 Ratings - R-407C (English Units) IPLV=14.2 YCAL0074EB AIR TEMPERATURE ON CONDENSER (°F) 75°F 80°F 85°F 90°F 95°F 100°F LCWT (°F) TONS EER TONS EER TONS EER TONS EER TONS EER TONS 75°F 70.1 11.7 72.9 74.4 10.8 70.8 79.0 68.7 83.8 66.5 88.9...
  • Page 29 FORM 150.62-EG1 (507) IPLV=14.2 YCAL0074EB AIR TEMPERATURE ON CONDENSER (°F) 105°F 110°F 115°F 120°F 125°F LCWT (°F) TONS EER TONS EER TONS EER TONS EER TONS 62.1 99.8 59.9 105.7 48.4 87.4 39.2 72.5 37.6 76.7 40.0 64.5 100.6 62.2 106.5 50.4 88.0...
  • Page 30 Ratings - R-407C (English Units) YCAL0104EB IPLV=14.0 AIR TEMPERATURE ON CONDENSER (°F) 75°F 80°F 85°F 90°F 95°F 100°F LCWT (°F) TONS EER TONS EER TONS EER TONS EER TONS EER TONS 99.3 91.7 11.6 96.6 96.8 10.8 93.8 102.2 10.0 91.0 108.1 88.0...
  • Page 31 FORM 150.62-EG1 (507) YCAL0104EB IPLV=14.0 AIR TEMPERATURE ON CONDENSER (°F) 105°F 110°F 115°F 120°F 125°F LCWT (°F) TONS EER TONS EER TONS EER TONS EER TONS 81.7 128.9 78.4 137.1 74.9 146.1 71.1 156.0 43.1 89.2 40.0 84.9 130.0 81.5 138.2 77.9 147.2...
  • Page 32: Ratings - R-407C (Si Units)

    Ratings - R-407C (SI Units) YCAL0014EB COP=3.69 AIR TEMPERATURE ON - CONDENSER (°C) 25°C 30°C 35°C 40°C 45°C 50°C LCWT (°C) 47.5 11.5 45.1 12.9 41.9 14.7 39.3 16.4 37.4 17.7 18.3 49.1 11.6 46.6 12.9 43.4 14.8 40.8 16.4 38.8 17.8 19.0...
  • Page 33 FORM 150.62-EG1 (507) YCAL004EB COP=4.13 AIR TEMPERATURE ON - CONDENSER (°C) 25°C 30°C 35°C 40°C 45°C 50°C LCWT (°C) 118.0 32.5 111.8 36.2 105.4 40.1 98.9 44.4 92.5 48.9 60.8 33.4 121.8 32.8 115.5 36.5 108.9 40.5 102.3 44.8 95.7 49.3 63.0 33.5...
  • Page 34 Ratings - R-407C (SI Units) YCAL0050EB COP=4.03 AIR TEMPERATURE ON - CONDENSER (°C) 25°C 30°C 35°C 40°C 45°C 50°C LCWT (°C) 178.1 48.7 169.3 54.2 160.1 60.1 150.7 66.7 105.8 50.7 71.2 36.2 184.2 49.1 175°F 54.5 165.5 60.6 155.9 67.1 109.5 51.0...
  • Page 35 FORM 150.62-EG1 (507) YCAL0074EB COP=4.17 AIR TEMPERATURE ON - CONDENSER (°C) 25°C 30°C 35°C 40°C 45°C 50°C LCWT (°C) 265.6 72.1 252.2 80.2 238.3 89.2 224.1 99.1 176.4 85.8 138.2 74.4 274.4 72.7 260.6 80.9 246.3 89.9 231.7 99.8 182.7 86.3 143.3 74.8...
  • Page 36 Ratings - R-407C (SI Units) YCAL0104EB COP=4.10 AIR TEMPERATURE ON - CONDENSER (°C) 25.0 30.0 35.0 40.0 45.0 50.0 LCWT (°C) 351.9 94.2 334.3 103.9 315.5 115.0 295.4 127.9 273.6 142.9 213.4 122.9 363.8 95.1 345.6 104.9 326.3 116.0 305.6 128.9 283.3 143.9 221.4 123.5 375.9...
  • Page 37 FORM 150.62-EG1 (507) INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
  • Page 38: Part Load Ratings - R-22 (English Units)

    Part Load Ratings - R-22 (English Units) YCAL0074EC YCAL000EC AMBIENT COMPR AMBIENT COMPR TONS TONS DISPL. DEG F DISPL. DEG F 100.0 95.0 76.0 86.4 100.0 95.0 82.2 95.3 84.3 88.0 67.1 66.2 11.0 83.3 87.5 71.9 69.9 11.3 66.7 79.3 56.1 43.9...
  • Page 39: Part Load Ratings - R-22 (Si Units)

    FORM 150.62-EG1 (507) Part Load Ratings - R-22 (SI Units) YCAL0074EC YCAL000EC AMBIENT UNIT COMPR AMBIENT UNIT COMPR DISPL. DEG C DISPL. DEG C 100.0 35.0 267.1 86.4 2.87 100.0 35.0 289.0 95.3 2.83 84.3 31.1 235.9 66.2 3.23 83.3 30.8 253.0 69.9...
  • Page 40: Part Load Ratings - R-407C (English Units)

    Part Load Ratings - R-407C (English Units) YCAL0014EB YCAL0020EB AMBIENT COMPR AMBIENT COMPR TONS TONS DISPL. DEG F DISPL. DEG F 100.0 95.0 12.7 14.8 100.0 95.0 17.4 21.2 50.0 69.7 13.7 50.0 70.1 10.2 14.1 IPLV:12.6 EER IPLV:12.9 EER YCAL0024EB YCAL000EB AMBIENT...
  • Page 41 FORM 150.62-EG1 (507) YCAL0074EB YCAL0080EB AMBIENT COMPR AMBIENT COMPR TONS TONS DISPL. DEG F DISPL. DEG F 100.0 95.0 71.6 90.3 100.0 5.0 78.0 100.0 84.3 88.6 63.9 69.1 10.1 83.3 88.0 68.9 73.6 10.3 66.7 80.3 54.1 45.9 12.3 66.7 80.3 58.9...
  • Page 42: Part Load Ratings - R-407C (Si Units)

    Part Load Ratings - R-407C (SI Units) YCAL0014EB YCAL0020EB AMBIENT UNIT COMPR AMBIENT UNIT COMPR DISPL. DEG C DISPL. DEG C 100.0 35.0 44.5 14.8 2.53 100.0 35.0 61.1 21.2 2.55 50.0 21.0 25.8 4.03 50.0 21.2 35.8 4.14 IPLV:3.69 COP IPLV:3.79 COP YCAL0024EB YCAL000EB...
  • Page 43 FORM 150.62-EG1 (507) YCAL0074EB YCAL000EB AMBIENT UNIT COMPR AMBIENT UNIT COMPR DISPL. DEG C DISPL. DEG C 100.0 35.0 251.8 90.3 2.59 100.0 35.0 274.4 100.0 2.57 84.3 31.4 224.8 69.1 2.96 83.3 31.1 242.2 73.6 3.01 66.7 26.9 190.3 45.9 3.61 66.7...
  • Page 44: Physical Data - (English Units)

    Physical Data - (English Units) Model Number YCAL 0014* 0020* 0024* 0030* 0034* 0040* 0042* 0044* General Unit Data Nominal Tons, R‑22 13.2 18.0 22.4 28.3 34.0 38.7 42.9 47.1 Nominal Tons, R‑407C 12.7 17.4 21.7 26.7 31.7 36.3 40.2 44.1 Number of Refrigerant Circuits Refrigerant Charge R‑22, ckt1 / ckt2, lbs 48/48 48/48 46/48...
  • Page 45 FORM 150.62-EG1 (507) Model Number YCAL 0050* 0060* 0064* 0070* 0074 0080 0090 0094 0104 0114 0124 0134 51.1 56.2 63.1 70.2 76.0 82.2 83.2 89.9 99.6 111.1 121.0 130.3 48.1 53.3 58.9 65.7 71.6 78.0 79.6 85.8 94.9 106.5 115.1 124.3 48/48...
  • Page 46: Physical Data - (Si Units)

    Physical Data - (SI Units) Model Number YCAL 0014* 0020* 0024* 0030* 0034* 0040* 0042* 0044* General Unit Data Nominal kW, R‑22 46.4 63.3 78.8 99.5 119.6 136.1 150.9 165.7 Nominal kW, R‑407C 44.7 61.2 76.3 93.9 111.5 127.7 141.4 155.1 Number of Refrigerant Circuits Refrigerant Charge R‑22, ckt1 / ckt2, kg 14.5 17.3 24.4...
  • Page 47 FORM 150.62-EG1 (507) Model Number YCAL 0050* 0060* 0064* 0070* 0074 0080 0090 0094 0104 0114 0124 0134 179.7 197.7 221.9 246.9 267.3 289.1 292.6 316.2 350.3 390.7 425.6 457.9 169.2 187.5 207.2 231.1 251.8 274.3 280.0 301.8 333.8 374.6 404.8 436.9 27.3/24.5...
  • Page 48: Dimensions - Ycal0014-Ycal0020 (English)

    Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
  • Page 49 FORM 150.62-EG1 (507) HFC-407c only 9 1/4" 1 1/2" POWER PANEL 51 1/2" 3/4" DIA. MOUNTING 37" HOLES (TYP.) CONTROL PANEL 1 1/2" 10 5/16" ORIGIN 78 7/16" TOP VIEW 9" 68 3/8" 29" 24 1/4" (2) 3" X 3" RIGGING 3"...
  • Page 50: Dimensions - Ycal0024-Ycal0034 (English)

    Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
  • Page 51 FORM 150.62-EG1 (507) HFC-407c only ����� � ����� � � � ����������� ���� ��� ��������� �������� ��� �������� ���� ������������� � � ����� � ���� ���� ������ ��������������������������������������� � �������� � � � � ���� ��� �� ��� ������� ������������������� �����...
  • Page 52: Dimensions - Ycal0040-Ycal0060 (English)

    Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
  • Page 53 FORM 150.62-EG1 (507) HFC-407c only 15 1/4" 1 1/2" POWER PANEL 80 1/2" 3/4" DIA. MOUNTING 50" HOLES (TYP.) 1,266 1,204 CONTROL PANEL 1 1/2" ORIGIN 99 1/2" 9 3/4" TOP VIEW 89 7/8" 9" 2 1/16" 29" 33 13/16" (2) 3"...
  • Page 54: Dimensions - Ycal0064-Ycal0080 (English)

    Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
  • Page 55 FORM 150.62-EG1 (507) HFC-407c for YCAL0064 and YCAL0070 models only 15 1/4" 1 1/2" POWER PANEL 80 1/2" 3/4" DIA. MOUNTING 50" HOLES (TYP.) CONTROL PANEL 1 1/2" ORIGIN 99 1/2" 9 3/4" TOP VIEW 89 7/8" 9" 2 1/16" 29"...
  • Page 56: Dimensions - Ycal0090-Ycal0094 (English)

    Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
  • Page 57 FORM 150.62-EG1 (507) 3/4" DIA. MOUNTING HOLES (TYP.) 1 1/4" 19 1/8" 88 1/4" POWER PANEL 50" CONTROL PANEL 1 1/4" ORIGIN 25 3/4" 34" 55 7/16" VIEW D-D 91 7/16" 29" 96" 38" 8" 8" (2) 3" X 3" WATER OUTLET WATER INLET RIGGING HOLES...
  • Page 58: Dimensions - Ycal0104 (English)

    Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
  • Page 59 FORM 150.62-EG1 (507) 3/4" DIA. MOUNTING HOLES (TYP.) 1 1/4" 19 1/8" 88 1/4" POWER PANEL 50" CONTROL PANEL 1 1/4" ORIGIN 31 5/8" 25 11/16" 38" 38" VIEW D-D 91 7/16" 29" 96" 38" ALUMINUM COPPER 8" 8" WATER OUTLET WATER INLET (2) 3"...
  • Page 60: Dimensions - Ycal0114 - Ycal0134 (English)

    Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
  • Page 61 FORM 150.62-EG1 (507) ALUMINUM COPPER Center of Gravity (in.) Center of Gravity (in.) YCAL YCAL 0114 83.3 45.2 45.3 0114 82.2 45.5 43.7 0124 82.3 45.9 44.7 0124 81.1 46.2 43.1 014 82.9 46.5 44.2 014 81.9 46.8 42.5 JOHNSON CONTROLS...
  • Page 62: Dimensions - Ycal0014-Ycal0020 (Si)

    Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
  • Page 63 FORM 150.62-EG1 (507) HFC-407c only POWER PANEL 1308 19 DIA. MOUNTING HOLES (TYP.) CONTROL PANEL ORIGIN 1993 TOP VIEW 1737 (2) 76 X 76 RIGGING 3" HOLES (EACH SIDE) 3" WATER OUTLET WATER INLET 1575 2043 2670 LD04871 SIDE VIEW ALUMINUM COPPER Center of Gravity (mm)
  • Page 64: Dimensions - Ycal0024-Ycal0034 (Si)

    Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
  • Page 65 FORM 150.62-EG1 (507) HFC-407c only POWER PANEL 1308 19 DIA. MOUNTING HOLES (TYP. ) CONTROL PANEL ORIGIN (* 1993) (** 1866) (*** 1866) TOP VIEW 2229 (2) 76 X 76 RIGGING (* 3") (** 4") HOLES (EACH SIDE) (*3") (** 4") WATER OUTLET WATER INLET (* 266) (** 291) (*** 285)
  • Page 66: Dimensions - Ycal0040-Ycal0060 (Si)

    Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
  • Page 67 FORM 150.62-EG1 (507) HFC-407c only POWER PANEL 2045 19 DIA. MOUNTING 1270 HOLES (TYP.) CONTROL PANEL ORIGIN 2527 TOP VIEW 2282 (2) 76 X 76 RIGGING 6" 6" HOLES (EACH SIDE) WATER OUTLET WATER INLET 2146 1791 3022 SIDE VIEW LD04875 ALUMINUM COPPER...
  • Page 68: Dimensions -Ycal0064-Ycal0080 (Si)

    Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
  • Page 69 FORM 150.62-EG1 (507) HFC-407c for YCAL0064 and YCAL0070 models only POWER PANEL 2311 19 DIA. MOUNTING 1270 HOLES (TYP.) CONTROL PANEL ORIGIN 2527 TOP VIEW 2473 (2) 76 X 76 RIGGING 6" 6" HOLES (EACH SIDE) WATER OUTLET WATER INLET 2159 1791 3022...
  • Page 70: Dimensions - Ycal0090-Ycal0094 (Si)

    Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
  • Page 71 FORM 150.62-EG1 (507) 19 DIA. MOUNTING HOLES (TYP.) 2241 POWER PANEL 1270 CONTROL PANEL ORIGIN 1408 VIEW D-D 2323 2438 8" 8" (2) 76 X 76 WATER OUTLET WATER INLET RIGGING HOLES 2108 (EACH SIDE) 2711 3581 3759 ALUMINUM COPPER Center of Gravity (mm) Center of Gravity (mm) YCAL...
  • Page 72: Dimensions - Ycal0104 (Si)

    Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
  • Page 73 FORM 150.62-EG1 (507) 19 DIA. MOUNTING HOLES (TYP.) 2241 POWER PANEL 1270 CONTROL PANEL ORIGIN VIEW D-D 2323 2438 8" 8" WATER OUTLET WATER INLET (2) 76 X 76 RIGGING HOLES (EACH SIDE) 2108 3169 4038 4216 ALUMINUM COPPER Center of Gravity (mm) Center of Gravity (mm) YCAL YCAL...
  • Page 74: Dimensions - Ycal0114 - Ycal0134 (Si)

    Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
  • Page 75 FORM 150.62-EG1 (507) COPPER ALUMINUM Center of Gravity (mm) Center of Gravity (mm) YCAL YCAL 0114 2115 1148 1151 0114 2087 1156 1110 0124 2059 1172 1094 0124 2089 1166 1135 014 2079 1189 1080 014 2106 1181 1121 JOHNSON CONTROLS...
  • Page 76: Weight Distribution

    Weight Distribution ALUMINUM FIN COILS English Units Aluminum Fin Coil Weight Distribution (lbs) YCAL Total 0014 2,548 0020 2,564 0024 2,940 000 3,036 004 3,381 0040 1,261 1,200 1,266 1,204 4,931 0042 1,283 1,223 1,274 1,214 4,994 0044 1,292 1,235 1,297 1,239 5,064...
  • Page 77 FORM 150.62-EG1 (507) COPPER FIN COILS English Units Copper Fin Coil Weight Distribution (lbs) YCAL Total 0014 2,762 0020 2,778 0024 3,275 000 3,371 004 3,717 0040 1,354 1,292 1,358 1,296 5,300 0042 1,375 1,315 1,366 1,307 5,363 0044 1,384 1,327 1,389 1,332...
  • Page 78: Isolator Selections - Aluminum Fin Coils

    Isolator Selections - Aluminum Fin Coils 1" DEFLECTION ISOLATOR SELECTION - VMC TYPE Aluminum Fin, 1” Isolator Selections VMC Type CP-x-xx YCAL 0014 CP-1-27 CP-1-26 CP-1-28 CP-1-27 0020 CP-1-27 CP-1-26 CP-1-28 CP-1-27 0024 CP-1-28 CP-1-27 CP-1-28 CP-1-28 000 CP-1-28 CP-1-27 CP-1-28 CP-1-28 004...
  • Page 79 FORM 150.62-EG1 (507) NEOPRENE ISOLATOR SELECTION - VMC TYPE Aluminum Fin, Neoprene Mount Selections VMC Type RD YCAL 0014 -3 Grn -2 Gray -3 Gray -3 Grn 0020 -3 Grn -2 Gray -3 Gray -3 Grn 0024 -3 Gray -3 Grn -3 Gray -3 Grn 000...
  • Page 80: Isolator Selections - Copper Fin Coils

    Isolator Selections - Copper Fin Coils 1" DEFLECTION ISOLATOR SELECTION - VMC TYPE Copper Fin, 1” Isolator Selections VMC Type CP-x-xx YCAL 0014 CP-1-27 CP-1-26 CP-1-28 CP-1-27 0020 CP-1-27 CP-1-26 CP-1-28 CP-1-27 0024 CP-1-28 CP-1-27 CP-1-31 CP-1-28 000 CP-1-28 CP-1-27 CP-1-31 CP-1-28 004...
  • Page 81 FORM 150.62-EG1 (507) NEOPRENE ISOLATOR SELECTION - VMC TYPE Copper Fin, Neoprene Mount Selections VMC Type RD YCAL 0014 -3 Grn -3 Grn -3 Gray -3 Grn 0020 -3 Grn -3 Grn -3 Gray -3 Grn 0024 -3 Gray -3 Gray -3 Gray -3 Gray 000...
  • Page 82: Isolators

    Isolators DIMENSIONS TYPE CP 1 LD03840 TYPE CP 2 ISOLATOR SPRING IDENTIFICATION TABLE 1" DEFLECTION SEISMIC MODEL PART- # COLOR MODEL PART # COLOR CP-1-26 308439-26 PURPLE AEQM-6 301055-96 BLACK CP-1-27 308439-27 ORANGE AEQM-7 301055-97 WHITE CP-1-2 308439-28 GREEN AEQM- 301055-98 GRAY CP-1-1...
  • Page 83 FORM 150.62-EG1 (507) DIMENSIONS MODEL # AEQM-7 5-1/2 4-1/2 2-1/2 7-1/4 AEQM- 5-1/2 4-1/2 2-1/2 7-1/4 AEQM- 5-1/2 4-1/2 2-1/2 7-1/4 AEQM-1000 8-1/2 6-1/2 4-1/2 8-3/8 AEQM-100 8-1/2 6-1/2 4-1/2 8-3/8 AEQM-1600 8-1/2 6-1/2 4-1/2 8-3/8 AEQM-1625 8-1/2 6-1/2 4-1/2 8-3/8 AEQM-162 8-1/2...
  • Page 84: Electrical Data

    Electrical Data NOTES: 1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If the optional Factory Mounted Control Transformer is provided, add the following MCA values to the electrical tables for the system providing power to the transformer: -17, add 2.5 amps;...
  • Page 85 FORM 150.62-EG1 (507) YCAL0014 - YCAL004 SINGLE POINT POWER SUPPLY CONNECTIONS (See Fig. 1) (One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused Disconnect Switch (optional) or Circuit Breaker (optional).) SINGLE POINT FIELD SUPPLIED WIRING SYSTEM #1 COMPRESSOR &...
  • Page 86: Electrical Data

    Electrical Data YCAL0040 - YCAL000 DUAL POINT POWER SUPPLY CONNECTIONS (See Fig. 2) Two Field Provided Power Supply Circuits to the chiller. Field connections to Factory Provided Terminal Blocks per system SYSTEM #1 FIELD SUPPLIED WIRING SYSTEM #1 COMPRESSOR & FAN INCOMING (LUGS) WIRE MODEL MIN N/F...
  • Page 87 FORM 150.62-EG1 (507) YCAL0040 - YCAL000 DUAL POINT POWER SUPPLY CONNECTIONS (See Fig. 2) Two Field Provided Power Supply Circuits to the chiller. Field connections to Factory Provided Terminal Blocks per system SYSTEM #2 FIELD SUPPLIED WIRING SYSTEM #2 COMPRESSOR & FAN CKT.
  • Page 88 Electrical Data –.continued YCAL0040 - YCAL000 SINGLE POINT POWER SUPPLY CONNECTIONS (see Fig. 1) (One Field Provided Power Supply Circuit to the chiller. Field connections to Factory Provided Terminal Block (optional), Non-Fused Disconnect Switch (optional) or Circuit Breaker (optional).) SINGLE POINT FIELD SUPPLIED WIRING INCOMING (LUGS) WIRE RANGE MODEL MIN N/...
  • Page 89 FORM 150.62-EG1 (507) YCAL0040 - YCAL000 SINGLE POINT POWER SUPPLY CONNECTIONS (see Fig. 1) (One Field Provided Power Supply Circuit to the chiller. Field connections to Factory Provided Terminal Block (optional), Non-Fused Disconnect Switch (optional) or Circuit Breaker (optional). SYSTEM #1 COMPRESSOR & FAN SYSTEM #2 FIELD SUPPLIED WIRING COMPR.
  • Page 90 Electrical Data –.continued YCAL0090 - YCAL0134 MULTIPLE POINT POWER SUPPLY CONNECTIONS (see Fig. 3) (Two Field Provided Power Supply Circuits to the chiller. Field connections to Factory Provided Terminal Blocks (standard), Non-Fused Disconnect Switches (op- tional), or Individual System Circuit Breakers (optional) per electrical system) SYSTEM #1 FIELD SUPPLIED WIRING MODEL VOLT...
  • Page 91 FORM 150.62-EG1 (507) YCAL0090 - YCAL0134 MULTIPLE POINT POWER SUPPLY CONNECTIONS (see Fig. 3) (Two Field Provided Power Supply Circuits to the chiller. Field connections to Factory Provided Terminal Blocks (standard), Non-Fused Disconnect Switches (op- tional), or Individual System Circuit Breakers (optional) per electrical system) SYSTEM #1 COMPRESSOR &...
  • Page 92 Electrical Data –.continued YCAL0090 - YCAL0134 SINGLE POINT POWER SUPPLY CONNECTIONS WITH INDIVIDUAL SYSTEM CIRCUIT BREAKERS (see Fig. 4) (One Field Provided Power Supply Circuit to the chiller. Field connections to Factory Provided Teminal Block (optional) or Non-Fused Disconnect Switch (optional). Includes Individual Branch Circuit Protection (Breakers) per electrical system) SINGLE POINT FIELD SUPPLIED WIRING MODEL...
  • Page 93 FORM 150.62-EG1 (507) YCAL0090 - YCAL0134 SINGLE POINT POWER SUPPLY CONNECTIONS WITH INDIVIDUAL SYSTEM CIRCUIT BREAKERS (see Fig. 4) (One Field Provided Power Supply Circuit to the chiller. Field connections to Factory Provided Teminal Block (optional) or Non-Fused Disconnect Switch (optional). Includes Individual Branch Circuit Protection (Breakers) per electrical system) SYSTEM #1 COMPRESSOR &...
  • Page 94: Power.wiring

    Power.Wiring FIG. 1 – STANDARD POWER SUPPLY WIRING – (YCAL 0014 - 0080) Figure 1: Single Point Supply Connection – Terminal Block, Non-Fused Disconnect Switch or Circuit Breaker (YCAL0043-0253) Power Panel Power Panel Power Panel Control Panel Control Panel Control Panel Terminal Block, Terminal Block, MICROPANEL...
  • Page 95 FORM 150.62-EG1 (507) Figure 3: Multiple Point Power Supply Connection – Terminal Block, Non-Fused Disconnect Switches or Circuit Breakers (YCAL0287-0377) Power Panel Power Panel Power Panel Control Panel Control Panel Control Panel MICROPANEL MICROPANEL Terminal Block1, Terminal Block1, Terminal Block2, Terminal Block2, NF Disconnect NF Disconnect...
  • Page 96: Control Wiring

    Control Wiring FLOW SW REMOTE START/STOP PWM INPUT LOAD LIMIT INPUT CTB1 * Factory wired with optional transformer. JOHNSON CONTROLS...
  • Page 97 FORM 150.62-EG1 (507) INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
  • Page 98: Application Data

    Application Data UNIT LOCATION not to damage the roof during installation. If the roof is “bonded”, consult the building contractor or architect The YCAL chillers are designed for outdoor installation. for special installation requirements. Roof installations When selecting a site for installation, be guided by the should incorporate the use of spring-type isolators to following conditions: minimize the transmission of vibration into the building...
  • Page 99: Guide Specifications

    FORM 150.62-EG1 (507) Guide Specifications PART 1 – GENERAL facturer. B. Unit shall be stored and handled per Manufacturer’s 1.01 SCOPE instructions. A. The requirements of the General Conditions, Sup- PART 2 - PRODUCTS plementary Conditions, Division 1, and Drawings apply to all Work herein.
  • Page 100 (optional), Fan Motors: High efficiency, direct drive, 6 pole, liquid temperature reset via a YORK ISN DDC 3 phase, insulation class “F”, current protected, or Building Automation System (by others) via...
  • Page 101 Some accessories and options supercede standard fan operation, run permissive status, number product features. Your YORK representative will be of compressors running, liquid solenoid valve pleased to provide assistance. status, load & unload timer status, water pump A.
  • Page 102 Single Point Circuit Break per remainder of unit cabinet. Heavy gauge, ers available on YCAL0014-0080 models. welded wire-mesh, coated to resist corrosion, around base of machine to restrict unauthorized D. Pressure Transducers and Readout Capability access.
  • Page 103 Available on D. Electrical: Coordinate electrical requirements and YCAL0014-0080 models. connections for all power feeds with Electrical Con- tractor (Division 16). V. OptiView Remote Control Panel (Field-mounted): Graphical interface panel to remotely control and E.
  • Page 104 Form 150.62-EG1 (507) Supersedes: 150.62-EG1 (205)