Electrical Connections - York YLCC-H Technical Information

Heat pumps and water chillers condensed by air, with centrifugal fans for indoor installation
Table of Contents

Advertisement

Accessories
Remote terminal
This accessory allows remote controlling and monitoring
of the unit (up to 040 m.). Functions are the same as the
standard keyboard of the control panel. The remote terminal
Wall mounting
For wall mounting it is necessary to fasten the rear support
(A) to a standard three-switch modular box.
- Fasten the rear of the casing to the box with the two round-
headed screws.

Electrical connections

Connect the RS485 serial device (separate accessory) to
the RJ2 power supply outlet (included with the remote ter-
minal) and to the monitoring connection of the electric panel
keyboard, using screened cable. Power terminals G-G0 by
means of a transformer and a 250 mAT fuse, following the
enclosed diagram. Connect the RJ2 power supply and
the remote terminal with the included telephone cable (80
Max. distance to the RS485
Speed
Cable characteristics
Cable section
Capacity per metre
50
is compatible with said keyboard of the control panel, and the
unit can be accessed from both devices. For application, it
must be interconnected to the system by means of the RS485
serial line connection accessory.
���
���
���
���
����
���������������
�����
- Connect the telephone cable.
- Rest the control unit on the rear casing and fasten with
the two flat-headed screws (B).
- Fasten the front panel by pressing lightly.
cm.). This cable can be replaced by a longer one of up to a
maximum of 40 m.
Attention:
- Use only safety transformers (3 VA, class 2).
- For safety purposes, a 250 mA slow fuse should be inserted
in series with terminal G.
- Do not ground the transformer secondary.
1 km. (insert a 120 ohm 1/4W resistor in the RS485)
19.200 bauds
2 twisted cables with shielding
AWG22 (0.35 mm²)
>90 pF/m (for example, BELDEN 8761-8762 cable)
���