York YLCC-H Technical Information page 41

Heat pumps and water chillers condensed by air, with centrifugal fans for indoor installation
Table of Contents

Advertisement

Display
Description
NTC B probe (water intake). 0 = absent (function not avai-
/01
lable).  = present
NTC B2 probe (water outlet ). 0 = absent (function not
/02
available).  = present
NTC B3 probe (liquid ). 0 = absent,  = present
/03
B4, B8 type probe, 0 = absent,  = ON/OFF, 2 = NTC, 3 =
/04/08
5 Vdc ratiometric
B5 type probe. 0 = absent (function not available).
/05
 = present
/06
NTC B6 probe (water outlet 2). 0 = absent,  = present
/07
NTC B7 probe (liquid 2). 0 = absent,  = present
/09
Minimum supply voltage
/10
Maximum supply voltage
/11
Minimum pressure
/12
Maximum pressure
/13
B probe calibration
/14
B2 probe calibration
/15
B3 probe calibration
/17/18
B5, B6 probe calibration
/19
B7 probe calibration
/16/20
B4, B8 probe calibration
/21
Digital filter
/22
Intake limitation
/23
Unit of measurement 0 = C;  = F
b00
Display read out probe (B)
b01
Value read by probe B, common water intake
b02
Value read by probe B2, water outlet circuit 
b03
Value read by probe B3, liquid circuit 
b04/05/08
Value read by probe B4
b06
Value read by probe B7, water outlet circuit 2
b07
Value read by probe B8, liquid circuit 2
Display
Description
c01
Minimum ON time
c02
Minimum OFF time
c03
Time between starts of the same compressor
c04
Time between starts of two compressors
c05
Time between stops of two compressors
c06
ON timing
c07
Compressor start delay with regard to the pump
c08
Pump OFF delay with regard to the compressor
c10/11
ON hour counter, compressors  and 2
c11/12
ON hour counter, compressors 3 and 4
c14
ON hour counter for compressor maintenance
c15
ON hour counter, pump
c17
Minimum time between pump starts
c18
Minimum pump ON time
Parameters related to probes
Level
Parameters related to the compressor
Level
VS
Unit
F
 (R/W)
-
F
2 (R/W)
-
F
4 (R/W)
-
5 (R/W)
F
-
7 (R/W)
F
3 (R/W)
-
F
4 (R/W)
-
F
6 (R/W)
-
F
8 (R/W)
0.0 Vdc
F
9 (R/W)
0.0 Vdc
F
 (R/W)
bar
F
2 (R/W)
bar
F
3 (R/W)
°C
F
4 (R/W)
°C
F
5 (R/W)
°C
F
6 (R/W)
°C
F
9 (R/W)
°C
F
0 (R/W)
bar
U
20 (R/W)
-
U
2 (R/W)
-
U
5 (R/W)
-
U
24 (R/W)
-
D
70 (R)
°C
D
7 (R)
°C
D
72 (R)
°C
D
73 (R)
°C/bar
D
76 (R)
°C
D
77 (R)
bar
VS
Unit
U
25 (R/W)
Sec.
U
26 (R/W)
Sec.
U
27 (R/W)
Sec.
U
28 (R/W)
Sec.
U
29 (R/W)
Sec.
U
30 (R/W)
Sec.
U
3 (R/W)
Sec.
U
32 (R/W)
Min.
D
90 (R)
Hours
D
9 (R)
Hours
U
34 (R/W)
Hours
D
94 (R/W)
Hours
U
35 (R/W)
Min.
U
36 (R/W)
Min.
Value
Max.
Min.
Pump
Cool
1
1

0

0
1
1
2
0
1
0
1
0
3
0
0
0

0

0
1
0
2
0
1
0
50
50
/0
0
500
/09
450
450
/2
0
0
0
34.5
34.5
99.9
/
2
-2
0
0
0
0
2
-2
2
-2
0
0
0
0
2
-2
2
-2
0
0
2
-2
0
0
4
4
5

5

8
8
0
0

0
7
0
0
0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Value
Max.
Min.
Pump
Cool
5
5
999
0
999
0
10
10
999
0
360
360
999
0
10
10
999
0
10
10
999
0
10
10
20
20
50
0
20
20
50
0
-
-
800
0
-
-
800
0
0
0
00
0
-
-
800
0
15
15
50
0
5
0
3
3
4