Clearances
When installing each unit, clearances should be left for:
- Air intake to the coil.
2- Water, drain and power supply connections.
3- Maintenance servicing.
Note: See minimum clearances indicated on the general
dimensions diagrams.
Drainage
The unit has two connections for draining condensed water
accumulated in the coil during operation in the winter cycle,
or for fully emptying the unit. The outer diameter of these
connections is 28 mm. At outdoor temperatures below 0°
C, condensed water can freeze and obstruct the drain. It is
advisable to take this into account and, when considered
necessary, install a flexible electric heater. This heater can
be connected by means of an ambient thermostat set to 3°
C, for example. This thermostat activates the heater when
�
�
�
�
Model
A
42
2 240
62
2 240
82
2 89
102
2 89
122
3 200
152
3 200
20
�
B
774
929
000
000
300
300
the temperature is below the set point.
Locating and securing the unit
These units are designed to be installed indoors. With air
discharge and return ducts, if necessary. Before opening
the packing, make sure you have received the appropriate
product by checking the specifications described on the
outside of same.
The unit should be placed on a perfectly horizontal plane,
making sure the base can support the weight of the unit.
If vibration-free operation is required, the unit can be placed
on a cork or similar anti-vibratory base, or fastened to the
base with anti-vibratory plates or supports (optional acces-
sory).
If the unit is to be placed on the floor, a concrete base should
be prepared so as to distribute weight evenly.
The following illustration shows the spaces and fastening
points that correspond to the location of each model.
Location dimensions
�
�
C
D
200
840
200
840
200
245.5 (x 2)
200
245.5 (x 2)
200
400 (x 2)
200
400 (x 2)
�
���������
���������
E
F
55
664
55
89
55
890
55
890
55
90
55
90
Ø G
6.5 (4)
6.5 (4)
6.5 (6)
6.5 (6)
6.5 (6)
6.5 (6)