Parameters Relating To Sensors - York YLHA 50 User Manual

Air-condensed water chillers and heat pumps
Hide thumbs Also See for YLHA 50:
Table of Contents

Advertisement

1
User manual
1.2
Operating instructions µC2 (YLHA 50, 60 and 80)

1.2.4 Parameters relating to sensors

Display
Description
NTC B1 sensor (water inlet):
0= Absent (function not available
/01
1= Present
NTC B2 sensor (water outlet):
0= Absent (function not available)
/02
1= Present
NTC B3 sensor (Outdoor temperature):
/03
0= Absent
B4 sensor:
0= Absent
1= ON/OFF
/04
2= NTC
3= Ratiometric 5 Vdc
B8-type sensor:
0= Absent
1= ON/OFF
/08
2= NTC
3= Ratiometric 5 Vdc
/09
Minimum input voltage
/10
Maximum input voltage
/11
Minimum pressure
/12
Maximum pressure
/13
B1 sensor calibration
/14
B2 sensor calibration
/15
B3 sensor calibration
/16
B4 sensor calibration (accessory)
/19
B7 sensor calibration
/20
B8 sensor calibration (accessory)
/21
Digital filter
/22
Input limitation
Measuring unit
0=C
/23
1=1F
b00
Sensor viewed on display
b01
Value read by sensor B1
b02
Value read by sensor B2
b03
Value read by sensor B3
b04
Value read by sensor B4
b07
Value read by sensor B7
b08
Value read by sensor B8
12
Parameters relating to sensors
Level
VS
Unit
F
1 (R/W)
F
2 (R/W)
F
14 (R/W)
F
15 (R/W)
F
F
18 (R/W)
0.01 Vdc
F
19 (R/W)
0.01 Vdc
F
1 (R/W)
bar
F
2 (R/W)
bar
F
3 (R/W)
°C
F
4 (R/W)
°C
F
5 (R/W)
°C
F
6 (R/W)
bar
F
°C
F
bar
U
20 (R/W)
U
21 (R/W)
U
5 (R/W)
U
24 (R/W)
D
70 (R)
°C
D
71 (R)
°C
D
72 (R)
°C
D
73 (R)
bar
D
76 (R)
°C
D
77 (R)
bar
Max.
Min.
-
1
0
-
1
0
-
1
0
-
3
0
-
3
0
/10
0
500
/09
/12
0
99,9
/11
12
-12
12
-12
12
-12
12
-12
12
-12
12
-12
-
15
1
-
15
1
-
1
0
-
7
0
-
-
-
-
-
-
-
-
-
-
-
-
Value
1
1
2
3
3
50
450
0
45
0
0
0
0
0
0
4
8
0
0
-
-
-
-
-
-