The following is a user's guide in the application and
installation of Millennium Chillers, and will ensure the reli-
ability and trouble-free life for which this equipment was
designed. while this guide is directed towards normal,
water-chilling applications, the Johnson Controls sales
representatives can provide complete recommendations
on other types of applications.
Location
Millennium Chillers are virtually vibration-free and gen-
erally can be located at any level in a building where
the construction will support the total system operating
weight.
The unit site must be a floor, mounting pad or foundation
which is level within 1/4" (6.4 mm) and capable of sup-
porting the operating weight of the chiller.
TABLE 1 – wATeR FLOw RATe LIMITS – GpM (L/s)
shELL
CodE
Pass
1
2
Ba
3
1
2
BB
3
1
2
Ca
3
1
2
CB
3
1
2
da
3
1
2
dB
3
1
2
dC
3
1
2
Ea
3
1
2
EB
3
1
2
EC
3
1
2
Fa
3
1
2
FB
3
1
2
FC
3

EVaPorator
MInIMuM
308
-19.4
1173
147
-9.3
586
97
-6.1
387
412
-25 8/9
1572
197
-12 2/5
786
130
-8 1/5
516
535
-33 4/5
2041
256
-16 1/5
1020
171
-10 4/5
680
700
-44.2
2675
335
-21.1
1337
223
-14.1
891
664
-41.9
2534
317
-20
1267
212
-13.4
844
943
-59.5
3602
451
-28.5
1793
301
-19
1195
1257
-79.3
4810
602
-38
2405
399
-25.2
1595
637
-40.2
2546
317
-20
1267
212
-13.4
844
904
-57
3613
452
-28.5
1805
301
-19
1196
1203
-75.9
4810
602
-38
2405
399
-25.2
1595
1203
-75.9
4810
602
-38
2405
399
-25.2
1595
1605
-101.3
6418
802
-50.6
3202
534
-33.7
2135
2136
-134.8
8541
1068
-67.4
4270
710
-44.8
2839
Sufficient clearance to permit normal service and mainte-
nance work should be provided all around and above the
unit. Additional space should be provided at one end of
the unit to permit cleaning of evaporator and condenser
tubes as required. A doorway or other properly located
opening may be used.
The chiller should be installed in an indoor location
where temperatures range from 40°F to 110°F (4.4°C to
43.3°C).
water Circuits
Flow Rate –
For normal water chilling duty, evaporator
flow rates are permitted at water velocity levels in the
heat exchangers tubes of between 3 ft./second and 12
ft./second (0.91 m/s and 3.66 m/s). Condenser flow rates
are permitted between 3.33 ft./sec. and 12 ft./sec. (1.01
m/s and 3.66 m/s). Variable flow applications are possible,
MaXIMuM
MInIMuM
-74
399
-37
209
-24.4
––
-99.2
510
-49.6
264
-32.6
––
-128.8
677
-64.4
355
-42 8/9
––
-168.8
880
-84.4
455
-56.2
––
-159.9
1215
-79.9
630
-53.3
––
-227.3
1595
-113.1
820
-175.4
––
-303.5
––
-151.8
––
-100.6
––
-160.6
1223
-79.7
639
-53.3
––
-228
1602
-113.9
828
-75.5
––
-303.5
––
-151.8
––
-100.6
––
-303.5
2019
-151.8
1043
-100.6
––
-405
2726
-202
1397
-134.7
––
-538.9
––
-269.4
––
-179.1
––
CondEnsEr
MaXIMuM
-25.2
1435
-13.2
751
––
––
-32 1/5
1830
-115.5
-16 2/3
948
-59 4/5
––
––
-42.7
2438
-153 4/5
-22.4
1277
-80 3/5
––
––
-55.5
3164
-28.7
1639
-103.4
––
––
-76.7
4376
-276.1
-39.8
2269
-143.2
––
––
-100.6
5740
-362.2
-51.7
2950
-186.1
––
––
––
––
––
––
––
––
-77.2
4406
-270.8
-40.3
2300
-145.1
––
––
-101.1
5770
-364.1
-55.2
2982
-188.2
––
––
––
––
––
––
––
––
-127.4
7267
-458.5
-65.8
3755
-236.9
––
––
-172
9822
-619.8
-88.2
5030
-317.4
––
––
––
––
––
––
––
––
JOHNSON CONTROLS
-90.5
-47.4
––
––
––
-80.6
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––