Selecting Relay Activation State

The middlemost C terminal and either one of the terminals NO/NC shall
be connected. The polarity can be freely selected.
NO
Normally open
C
Common relay
NC
Normally closed
Relay NOT activated: C and NC outputs are closed, NO is open
Relay IS activated:
Connect the power and close the cover. For instructions on how to
operate the relay (for example, select quantity for the relay output and set
the relay setpoints) see section Operation of Relays on page 112.
Figure 32
Relay Module
Numbers refer to Figure 32 above:
1
=
Indication led for the relay 1 or 3
2
=
Relay test buttons
3
=
Flat cable pins
4
=
Indication led for relay 2 or 4
The relay module may contain dangerous voltages even if the transmitter
power has been disconnected. Before working on the relay module you
must switch off both the transmitter and the voltage connected to the
relay terminals.
Do not connect the mains power to relay unit without grounding the
transmitter.
C and NO outputs are closed, NC is open.
0605-032