Chapter 4 ________________________________________________________________ Operation
VAISALA _______________________________________________________________________ 19

Setting Relay Trigger Points

The relays of the transmitter turn
reaches the predefined trigger point. There are two trigger points for
both relays. The higher limit activates the relay and the lower
deactivates it. The two limits are used to prevent the relay switching
back and forth when the measured value is very close to set point.
Both commands can also be entered without entering a trigger point
value. The command withour parameters gives the current set value.
MF_Rx_HIGH yyy<cr>
where:
x = 1 or 2 (number of the relay)
yyy = trigger point (CO
Example of setting the higher trigger limit of the relay 1:
>MF_R1_HIGH 1200
MF_R1_HIGH=1200.0000
>
Save the settings:
MAIN_SAVE F<cr>
Give the lower trigger limit:
MF_Rx_LOW yyy<cr>
where:
x= 1 or 2 (number of the relay)
yyy = trigger point (CO
Example of setting the lower trigger limit of the relay 1:
>MF_R1_Low 900
MF_R1_LOW=900.000000
>
Save the settings:
MAIN_SAVE F<cr>
/
when the CO
ON
OFF
content in ppm)
2
content in ppm)
2
content
2