Table 48 230V Wattage and BTU/Hour (continued)
Enclosures
2
4.0
1
2.3
Table 49 100V Wattage and BTU/Hour
Enclosures
Amps
8
7
6
5
4
18.7
3
14.8
2
10.8
1
6.8

UPS Selection

This section provides information that can be used when selecting a UPS for use with the EVA. The
four HP UPS products listed in
included in this comparison.
power under varying loads and with various UPS ERM (Extended Runtime Module) options.
The load imposed on the UPS for different disk enclosure configurations are listed in
147),
Table 53 (page
NOTE:
The specified power requirements reflect fully loaded enclosures (14 disks) .
Table 50 HP UPS models and capacities
Table 51 UPS operating time limits
Load (percent)
100
80
50
20
146 Non-standard rack specifications
EVA4x00
916
883
3014
526
507
1729
EVA4x00
VA
Watts
BTU/h
1875
1837
6269
1475
1446
4933
1075
1054
3596
676
662
2259
Table 50 (page 146)
Table 51 (page 146)
147), and
Table 54 (page
UPS Model
R1500
R3000
R5500
R12000
With standby battery
5
6
13
34
EVA6x00
4.3
989
953
3253
2.6
598
577
1968
EVA6x00
Amps
VA
Watts
BTU/h
35.5
3545
3474
1 1855
31.5
3145
3082
10518
27.5
2746
2691
9181
23.5
2346
2299
7845
19.5
1946
1907
6508
15.5
1546
1516
5171
1 1.5
1 147
1 124
3835
7.5
747
732
2498
are available for use with the EVA and are
identifies the amount of time each UPS can sustain
148).
Capacity (in watts)
Minutes of operation
With 1 ERM
R1500
23
32
57
146
R3000
EVA8x00
4.6
1062
1023
2.9
671
647
EVA8x00
Amps
VA
Watts
EVA8x00 not supported
Table 52 (page
1340
2700
4500
12000
With 2 ERMs
49
63
161
290
3492
2207
BTU/h

Hide quick links: