What's in the Package
Backup Interface
Mounting bracket
SAFETY AND HANDLING INSTRUCTIONS
Read this entire document before installing or operating the Backup Interface (also referred to as BUI). Failure to do so or to follow any of the
instructions or warnings in this document can result in electrical shock, serious injury, or death, or may damage the Backup Interface and
other property, it can also lead to warranty void.
Do not discard this document! After installation, keep it adjacent to the Backup Interface for future reference!
Before operating the Backup Interface and inverter, ensure that they are properly grounded. The Backup Interface and inverter must be
connected to a grounded, metal, permanent wiring system, or an equipment-grounding conductor must be run with the circuit conductors
and connected to the equipment grounding terminal or lead.
Opening the Backup Interface and repairing or testing under power must be performed only by qualified service personnel familiar with the
Backup Interface.
WARNING
!
The backup systems generate power to the home when the grid is off or when the main circuit breaker is also OFF. Please make sure to
attach the warning sticker (of Dual Supply warning) in a visible place at the main circuit cabinet. For additional safety, we recommend
installing an external shutdown press button to make sure the Inverter is also turned off when the main circuit breaker is off.
For installation instructions please refer to the Inverter installation guide.
Main connection scheme
WARNING!
Connect the Neutral of the
load here ONLY if you are
using TN-C-S, AND your local
regulation prohibits
connection of the load
Neutral to the local PE
1
4
4
Scan for Backup
Scan for Backup
Interface
Interface commissioning:
commissioning video:
Lower bracket
Warning Label
WARNING!
In case using TT or TN-S AND
local regulation mandate
connect the local grounding to
the Island Neutral, then connect
the Load side Neutral here to
create a short between local PE
and Neutral (local PEN)
Mounting the Backup
Interface
1.
Select an installation location. Make sure you have enough
3
space between the Backup Interface and other objects to
securely access all its interfaces.
2.
Install the mounting bracket to the wall and secure it with
2-4 screws. If using only 2 screws, use left and right ones.
3.
Hang the Backup Interface on the mounting bracket.
2
4.
Hang the lower bracket on the hook behind the bottom
glands, secure it to the wall with a screw.
Quick Installation Guide
Required Tools
Phillips
screwdriver
Drill
M4, M5 Allen
CAT6 cable
keys
BACKUP POWER DESIGN GUIDE
The design of backup power is limited only to the SolarEdge Home Hub Inverter Single Phase, operating as a backup Inverter,
and the availability of a standard code three phase grid (not a generator). The backup system cannot operate as an OFF-grid-
only system.
The following design configuration options are available:
Full House Backup (FHB) – In this configuration, all home loads can operate in backup mode and are limited to the Inverter
power during Backup.
Partial House Backup (PHB) - In this configuration, only part of the home loads can operate in backup mode and are limited
to the Inverter power during Backup.
For detailed design and configuration options, refer to:
single-phase-inverter-supported-use-cases-for-storage-and-backup-installations-application-note.pdf
WARNINGS
This symbol on the product or in the accompanying documentation denotes a hazard. It calls attention to a procedure
that, if not correctly performed or adhered to, could result in injury or loss of life. Do not proceed beyond a warning
note until the indicated conditions are fully understood and met.
This symbol on the product denotes risk of electric shock due to stored energy. Before handling the product,
wait for at least 5 seconds after disconnecting it from all sources of energy.
DANGER!
It is forbidden and dangerous to open the upper section. Use only the lower section for interface connections.
Before opening the covers and connecting the grid, please make sure that the main CB and the Inverters are OFF.
Bottom interface of the Backup Interface
Load section
Grid section
2
1
SolarEdge Home
Backup Interface,
Single Phase
BI-EU1P
for use with the SolarEdge Home
Hub Inverter, Single Phase
Level
Watchmaker
flat screwdriver
X 3
Pencil
Mounting screws
and wall plugs
https://knowledge-center.solaredge.com/sites/kc/files/se-home-hub-
!
Removing the covers
DANGER!
It is forbidden and dangerous to open the upper section.
Use only the lower section for interface connections.
Before opening the covers and connecting the grid, please
make sure that the main CB and the Inverters are OFF.
1.
Using M5 Allen key, release six screws and remove the Backup
Interface front cover.
2.
Using M4 Allen key, release two screws and remove the Backup
Interface internal lower cover.
3.
Make sure the ON/OFF switch is in the OFF position.
2
3
Torque wrench
OFF

Advertisement

loading

Summary of Contents for SolarEdge BI-EU1P

  • Page 1 Warning Label The design of backup power is limited only to the SolarEdge Home Hub Inverter Single Phase, operating as a backup Inverter, and the availability of a standard code three phase grid (not a generator). The backup system cannot operate as an OFF-grid- only system.
  • Page 2 Grid Connection 6 N*m Option 1 Load connection TT/TN-S Neutral: Short with the Ground (TT/TN-S) Option 2 6 N*m Load connection TN-C-S Note: Strip the ground/load cables to 12-150mm Regular Neutral ( TN-C-S) Note: If your local grid Scan for the Home Hub operator provides a inverter installation guide TN-C connection, refer...