Immergas VICTRIX HYBRID Instructions And Recommendations page 97

Hide thumbs Also See for VICTRIX HYBRID:
Table of Contents

Advertisement

Id
Parameter
Parameter
Max DHW
P0
output
P1
Min CH output
P2
Max CH output
UI P.C.B. relay
P3
operation
Pump function-
P4
ing
External probe
P5
correction
P6
-
P7
-
Three way delay
P8
standby OFF UE
Description
Defines the maximum heat output percentage of the Indoor
Unit during the DHW mode compared to the maximum
heat output available
Defines in percentage the minimum output in central
heating mode
Defines the maximum heat output percentage of the Indoor
Unit during the central heating mode compared to the
maximum heat output available
0 = OFF
1 = Not available
2 =General alarm
3 = CH phase mode
4 = External gas valve power supply
5 = Not available
6 = U.I. circulator command
7= Not available
8 = Not available
9 = Not available
10 = Not available
Set this parameter from the control panel. see Par. 3.6
If the reading of the external probe is not correct it is possible
to correct it in order to compensate any environmental
factors.
Not available for this model
Not available for this model
Management of three-way commutation delay for UE switch
of standby
Range
Default
0 - 100 %
100 %
0 - P2
0 %
VICTRIX
24HY
G20 = 85
G31 = 82
0 - 100 %
VICTRIX
32HY
G20 = 85
G31 = 85
0 - 10
0
-9 ÷ 9 K
0
-
-
-
-
0 - 30
7
Customised
value
97

Advertisement

Table of Contents
loading

This manual is also suitable for:

Victrix hybrid 323.030698

Table of Contents