Immergas VICTRIX HYBRID Instructions And Recommendations page 88

Hide thumbs Also See for VICTRIX HYBRID:
Table of Contents

Advertisement

Menu item
External probe enabling Defines the use of the external probe.
With the external probe not in use it defines the minimum flow
temperature that can be set by the user. With the external probe
Flow set heat min
enabled it defines the minimum flow temperature correspond-
ing to operation with maximum external temperature
Without the external probe it defines the maximum flow
temperature that can be set by the user. With the external probe
Flow set heat max
present it defines the maximum flow temperature correspond-
ing to operation with minimum external temperature
With the external probe enabled it defines at what external
External min temp.
temperature the system must operate at the maximum flow
temperature
With the external probe present it defines at what maximum
External max temp.
external temperature the system must operate at the minimum
flow temperature
It enables you to set operation of the control panel as ON/OFF or
modulating. Set "Yes", the flow temperature will be varied
depending on the room temperature set. Set "No", the flow
temperature will be kept constant until the desired room
Room probe modul.
temperature is reached.
N.B.: if an outdoor temperature probe is enabled, the flow
temperature will be set depending on the relative functioning
curve.
It establishes the system reaction speed according to the type of
system present.
Example:
System inertia
5 system with little heat inertia
10 system with normal dimensions with radiators
20 system with a lot of heat inertia (e.g. floor-standing system)
Antifreeze enable
Enables the room antifreeze function
Allows to set the room temperature for activation of the
Antifreeze set
anti-freeze function.
O.U. antifreeze disable
Do not use
88
"Service" -> "Thermoregulation" menu
Description
Range
Default
Yes / No
Yes
20 ÷ 45
30
35 ÷ 80
50
-25 ÷ +15 °C
-5
-5 ÷ +45 °C
25
Yes / No
Yes
1 ÷ 20
10
Yes / No
Yes
3 ÷ 10 °C
5 °C
--
--
Customised
value