Electrical Notes; Table 12 - Typical Compressor Starting Current (First Four Seconds Of Start-Up); Table 13 - Voltage Utilization Range - York YCIV0157 Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

Section 6 - Technical data

Electrical notes

1. As standard, all units have single point power con-
nection. Contact factory for information regarding
dual point power units.
2. Maximum Inverse Time Circuit Breaker or Dual
Element Fuse - 225% of the largest compressor
RLA plus the sum of all the other loads per NEC
440.22 (A).
3. MCA - Minimum Circuit Ampacity - 125% of the
largest compressor RLA plus 100% of the remain-
ing compressor RLA's plus the sum of all con-
denser fan FLA's per NEC 440.33

Table 12 - Typical Compressor Starting Current (First Four Seconds Of Start-Up)

Rated Voltage
380-400/50/3
380/60/3
460/60/3

Table 13 - Voltage Utilization Range

Rated Voltage
380-415/50/3
380/60/3
460/60/3
NOTES:
1. U.L. Label is provided on 60 Hz units for these electrical wiring configurations.
2. –– –– –– –– –– –– Dashed Line = Field Provided Wiring.
3. The above recommendations are based on the National Electric Code and using copper conductors only. Field wiring must also comply with
local codes. Group Rated breaker must be HACR type for cUL machines.
Electrical Notes - Legend
C.B.
D.E.
DISC SW
FACT CB
Factory-Mounted Circuit Breaker
FLA
Hz
MAX
MCA
Minimum Circuitry AMPACITY
MIN
MIN NF
RLA
S.P. WIRE
84
Circuit Breaker
Dual Element Fuse
Disconnect Switch
Full Load AMPS
Hertz
Maximum
Minimum
Minimum Non Fused
Rated Load AMPS
Single Point Wiring
4. Recommended time delay or dual element fuse
size - 150%of the largest compressor RLA plus
100% of the remaining compressor RLA's plus
the sum of all condenser fan FLA's.
5. RLA - Rated Load Amps - rated in accordance
with UL standard 1995.
6. Local codes may take precedence.
7. Control KVA includes operational controls and
evaporator heaters.
8. System inrush current is less than RLA due to the
use of York Variable Speed Drive technology.
Typical Starting Current per Compressor
28 A
29 A
23 A
Utilization Range
360-440
342-402
414-508
Form 201.23-NM2
Issue date: 12/19/2023