Table 12: Electrical data without pumps, R-454B, continued
YLAA
V
Hz MCA Min. N/F
208
60
734
230
60
731
200
380
60
443
460
60
369
575
60
292
208
60
904
230
60
902
230
380
60
498
460
60
472
575
60
339
Johnson Controls
Min. dual
Max. dual
disc SW
elem. fuse
elem. CB
and CB
1,000
800
800
1,000
800
800
600
500
500
600
400
400
400
300
300
1,200
1,000
1,000
1,200
1,000
1,000
600
500
500
600
500
500
400
350
350
System 2
Compr. 1
Compr. 2
RLA
LRA
RLA
LRA
RLA
102.8 635 102.8 635 102.8 635
102.8 635 102.8 635 102.8 635
62.2
355
62.2
355
62.2
51.4
316
51.4
316
51.4
41.1
258
41.1
258
41.1
130.1 761 130.1 761 130.1 761
130.1 761 130.1 761 130.1 761
71.1
475
71.1
475
71.1
67.9
344
67.9
344
67.9
48.7
296
48.7
296
48.7
Section 5: Technical data
Compr. 3
Std. flow fans
LRA
Qty.
FLA
LRA
6
7.6
44
6
7.4
37
355
6
4.5
23.1
316
6
4
19
258
6
2.9
15.3
6
7.6
44
6
7.4
37
475
6
4.5
23.1
344
6
4
19
296
6
2.9
15.3
5 5
69