Table 5: Ethylene And Propylene Glycol Correction Factors - York YLAA0041 Installation Operation & Maintenance

Air-cooled scroll chillers with brazed plate heat exchanger style b (60 hz) 4 to 12 fan 40 ton to 230 ton 140 kw to 800 kw
Hide thumbs Also See for YLAA0041:
Table of Contents

Advertisement

Form 150.72-ICOM6
Issue date: 12/19/2023

Table 5: Ethylene and Propylene Glycol Correction Factors

ETHYLENE GLYCOL
%
COMPR
TONS
KW
WEIGHT
10.0
1.0
1.0
20.0
1.0
1.0
30.0
1.0
1.0
40.0
1.0
1.0
50.0
1.0
1.0
NOTE: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges.
Johnson Controls
GPM F/
PRESS
FREEZE
TON
DROP
PT
24.3
1.0
26.2
25.1
1.1
17.9
25.9
1.2
6.7
26.9
1.4
-8.1
28.0
1.6
-28.9
PROPYLENE GLYCOL
%
COMPR
TONS
KW
WEIGHT
10.0
1.0
1.0
20.0
1.0
1.0
30.0
1.0
1.0
40.0
1.0
1.0
50.0
0.9
1.0
Section 5: Technical data
GPM F/
PRESS
FREEZE
TON
DROP
PT
24.0
1.0
26.0
24.3
1.1
19.0
24.9
1.3
9.0
25.6
1.4
-6.0
26.6
1.7
-28.0
49
5 5