Optional Printer Installation - York YLAA0041 Installation Operation & Maintenance

Air-cooled scroll chillers with brazed plate heat exchanger style b (60 hz) 4 to 12 fan 40 ton to 230 ton 140 kw to 800 kw
Hide thumbs Also See for YLAA0041:
Table of Contents

Advertisement

Form 150.72-ICOM6
Issue date: 12/19/2023
Table 34: Data logging to flas, continued
Data
Header
Number
Text
75
S1 Prop Cont In
76
S1 Int Cont In
77
S1 Der Cont In
78
S2 Full PID Index
79
S2 Dim PID Index
80
S2 Alg Ctrl Act
81
S2 Sheat Ex In
82
S2 Prop Cont In
83
S2 Int Cont In
84
S2 Der Cont In
85
S1 Thr Limit
86
S2 Thr Limit

Optional printer installation

The micro panel can supply a printout of chiller con-
ditions or fault shutdown information at any given
time. Operators and service personnel can access this
data and system status information using the keypad.
In addition to manual print selection, the micro panel
provides an automatic printout whenever a fault oc-
curs. Detailed explanation of the print function is
given under Print key on page 147.
Johnson Controls
Unit
Format
Sys 1 CSHALG_PROPORTIONAL_CONTRIBUTION_INDEX
x
(0-10000 in x100 format)
Sys 1 CSHALG_INTEGRAL_CONTRIBUTION_INDEX
x
(0-1000000 in x10000 format)
Sys 1 CSHALG_DERIVATIVE_CONTRIBUTION_INDEX
x
(0-10000 in x100 format)
Sys 2 CSHALG_FULL_PID_ACTIVE_INDEX
x
(0 = Disable, 1 = Active)
Sys 2 CSHALG_DIMINISHED_PID_ACTIVE_INDEX
x
(0 = Disable, 1 = Active)
Sys 2 CSHALG_ALGORITHM_CONTROL_ACTIVE
x
(0 = Disable, 1 = Enable)
Sys 2 CSHALG_SUPERHEAT_EXCURSIONS_INDEX
x
(0 – 255 in x1 format)
Sys 2 CSHALG_PROPORTIONAL_CONTRIBUTION_INDEX
x
(0-10000 in x100 format)
Sys 2 CSHALG_INTEGRAL_CONTRIBUTION_INDEX
x
(0-1000000 in x10000 format)
Sys 2 CSHALG_DERIVATIVE_CONTRIBUTION_INDEX
x
(0-10000 in x100 format)
%
x
Sys 1 CSHALG_EEV_THROTTLE_LIMIT (0-10000 in x100 format)
%
x
Sys 2 CSHALG_EEV_THROTTLE_LIMIT (0-10000 in x100 format)
Section 9: Service and troubleshooting
Data
Value Description
Parts
The following parts are required:
1. Printer.
2. Desk top calculator paper, 2.25 in. (5.7 cm) wide.
3. Twisted Pair Shielded Cable (minimum 3 conduc-
tor), #18 AWG stranded, 300 V minimum insula-
tion, 25 ft (7.62 m) maximum length.
4. One 25 pin Cannon connector and shell.
5. Cannon P/N DB-25P connector, or equivalent.
6. Cannon P/N DB-C2-J9 shell.
9
195

Advertisement

Table of Contents
loading

Table of Contents