Section 7: Unit controls

Table 15: YLAA Fault and Inhibit Codes

Code
Type
2
Unit Fault
4
Unit Fault
22
Unit Fault
27
Unit Fault
28
Unit Fault
29
Unit Fault
31
Unit Fault
5
System Fault
7
System Fault
17
System Fault
18
System Fault
19
System Fault
23
System Fault
24
System Fault
25
System Fault
26
System Inhibit
30
System Inhibit
32
System Inhibit
33
System Inhibit

Table 16: Legend

Type
3x
Automatically restarts on the first and second fault with a lockout on the third fault in 90 minutes
1x
Locks out on the first fault
Auto
Allows restart once meeting the required conditions
142
Fault or Inhibit Description
Low Ambient Temperature
Low Leaving Chilled Liquid Temperature
Unit High Motor Current (Unit Current Feedback Option)
Pump Trip (Hydro Pumps 1 or Hydro Pumps 2)
Pump Flow Failure (Hydro Pumps 1 or Hydro Pumps 2)
High Ambient Temperature
Flow Switch Open
High Discharge Pressure (Software)
Low Suction Pressure
System High Motor Current (System Current Feedback option)
Motor Protector/High Pressure (Mechanical)
Low Evaporator Temperature (R407c Only - N/A Hp Heating Mode)
Low Suction Superheat (EEV)
Sensor Failure (EEV)
Discharge Inhibit (Heat Pump heating mode only)
Motor Protector/High Pressure Inhibit
Anti-Vacuum Low Pressure Cutout
Leaving Chilled Liquid Temperature Sensor Fault
Low Discharge Superheat
Definition
Form 150.72-ICOM6
Issue date: 12/19/2023
Auto, 1x, 3x
See Table 16
Auto
Auto
Auto
Auto
1x
Auto
Auto
3x
3x
3x
3x
3x
3x
1x
3x
Auto
3x
3x
Auto